6. External View of P.C. Board
7. Address Setup
In addition to set up the central control address, it is necessary to change the indoor unit number.
(Line/Indoor/Group address).
For details, refer to TCC-LINK Adapter Installation Manual.
12-3. How to set up central control address number
When connecting the indoor unit to the central control remote controller using TCC-LINK adapter, it is neces-
sary to set up the central control address number.
• The central control address number is displayed as the line No. of the central control remote controller.
1. Setup from remote controller at indoor unit side
* If you use the network adapter P.C. board, it is effective only when No. 7 of setup switch SW01 on P.C.
board is turned off.
<Procedure> Perform setup while the unit stops.
1
Push 
TEST
 + 
VENT
 buttons for 4 seconds or more.
When group control is executed, first the unit No. 
RLL
 is displayed and all the indoor units in the group
control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)
(Keep 
RLL
 displayed status without pushing 
UNIT
 button.)
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address
are displayed.
2
Using temperature setup 
TEMP.
 buttons, specify item code 
03
.
3
Using timer time 
TIME
 buttons, select the setup data. The setup data is shown in the right
table (Table 1).
4
Push 
SET
 button. (OK if display goes on.)
• To change the item to be set up, return to Procedure 
2
.
5
Push 
TEST
 button.
The status returns to usual stop status.
5
2
1
1   
3   
4   
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
UNIT   No.
DATA
SET
R.C.
No.
(Table 1)
Setup data
0001
0002
0003
:
0064
0099
Central control address No.
1
2
3
:
64
Unset (Setup at shipment from factory)
(Fig.1)
Terminator (SW01)
52