9-4. Applicable Control of Outdoor unit
The following controls are enabled by connecting the part “Application control kit” (TCB-PCOS1E2) sold
separately.
(1) Power peak cut control
* The capacity of the outdoor unit is saved by the Demand signal from outside and corresponds to the
temporary peak cut.
* The capacity save is switched to 3 stages, 75%, 50% and operation stop.
(2) Night operation (Sound reduction)
* Input a timer on the market (Arranged at site). The capacity is lowered regardless of load and the operation
noise is reduced until 45dB. However the normal control is carried out if the outside temperature (TO sensor
value) is 40°C or more.
(3) Compressor operation output
* When the compressor drives, turn on the contact output of no voltage.