4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
SM160
High
Low
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
250
260
260
320
380
480
500
530
610
640
660
720
720
720
780
240
300
400
500
520
550
630
660
700
740
740
740
820
1) Cooling fan control
Q
The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the opera-
tion.  The outdoor is controlled by every 1 tap of DC fan control (15 taps).
R
Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap
which corresponds to the zone in the following table.
After then the fan is controlled by TE sensor temperature.
S
Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution
frequency of the fan increases regardless of TE if temperature of TD sensor has risen.
(The operation frequency differs according to the model type.)
SM160
a
b
37
34
+1 tap/20 seconds
rpm hold
–1 tap/20 seconds
Operation with
maximum tap in
each zone
Usual fan control
a
b
TE [˚C]
TD [˚C]
85
80
75
65
Operation with WE
Temp. range
 29°C < TO
15 < TO < 29°C
  5 < TO < 15°C
  0 < TO <   5°C
–5 < TO <   0°C
TO < –5°C
     TO error
Below 30Hz
Above 30 Hz below 45 Hz
Above 45 Hz
Min.
Max.
Min.
Max.
Min.
Max.
W5
WA
W7
WC
W9
WE
W3
W7
W5
W9
W7
WB
W2
W5
W4
W7
W6
W9
W1
W3
W3
W5
W4
W7
W1
W2
W2
W4
W3
W5
OFF
OFF
OFF
W3
OFF
W3
W1
WE
W1
WE
W1
WE