Справочник Пользователя для Toshiba RAS-10YAV-E
– 40 –
Discharging position
(Discharging period
10 seconds or more)
(Discharging period
10 seconds or more)
Plug of
soldering iron
soldering iron
Inverter cover
P. C. board
(Soldered surface)
(Soldered surface)
MCC-808
10. HOW TO DIAGNOSE THE TROUBLE
The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose
troubles according to the trouble diagnosis proce-
dure as described below. (Refer to the check points
in servicing written on the wiring diagrams attached
to the indoor/outdoor units.)
indoor and outdoor units. Therefore, diagnose
troubles according to the trouble diagnosis proce-
dure as described below. (Refer to the check points
in servicing written on the wiring diagrams attached
to the indoor/outdoor units.)
Table 10-1
No.
Troubleshooting Procedure
Page
1
First Confirmation
40
2
Primary Judgment
41
3
Judgment by Flashing LED of Indoor Unit
42
4
Self-Diagnosis by Service Check Remote
43
Controller
5
Judgment of Trouble by Every Symptom
46
6
How to Check Simply the Main Parts
53
NOTE :
A large-capacity electrolytic capacitor is used in the
outdoor unit controller (inverter). Therefore, if the
power supply is turned off, charge (charging voltage
DC280V) remains and discharging takes a lot of
time. After turning off the power source, if touching
the charging section before discharging, an electri-
cal shock may be caused. Discharge the electrolytic
capacitor completely by using soldering iron, etc.
outdoor unit controller (inverter). Therefore, if the
power supply is turned off, charge (charging voltage
DC280V) remains and discharging takes a lot of
time. After turning off the power source, if touching
the charging section before discharging, an electri-
cal shock may be caused. Discharge the electrolytic
capacitor completely by using soldering iron, etc.
< Discharging method >
(1) Remove the inverter cover (plating) by opening
four mounting claws.
(2) As shown below, connect the discharge resis-
tance (approx. 100
Ω
40W) or plug of the solder-
ing iron to voltage between + – terminals of the
C14 (“CAUTION HIGH VOLTAGE 320V” is
indicated.) electrolytic capacitor (500µF/400V)
on P.C. board, and then perform discharging.
C14 (“CAUTION HIGH VOLTAGE 320V” is
indicated.) electrolytic capacitor (500µF/400V)
on P.C. board, and then perform discharging.
Fig. 10-1
10-1. First Confirmation
10-1-1. Confirmation of Power Supply
Confirm that the power breaker operates (ON)
normally.
normally.
10-1-2. Confirmation of Power Voltage
Confirm that power voltage is AC 220–230–240 ±
10%. If power voltage is not in this range, the unit
may not operate normally.
10%. If power voltage is not in this range, the unit
may not operate normally.