Справочник Пользователя для Toshiba RAS-10YKV-E
– 19 –
NOTE :
• The maximum pipe length of this air conditioner is 15 m. The additional charging of refrigerant is unneces-
sary because this air conditioner is designed with charge-less specification.
Deoxidized copper pipe
Outer dia. : 9,52mm
Thickness : 0,8mm
Thickness : 0,8mm
NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1
Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6,35mm
Thickness : 0,8mm
Outer dia. : 6,35mm
Thickness : 0,8mm
Sectional shape
of heat insulator
of heat insulator
Allo
w
a
b
le height
diff
erence :
10m
Allo
w
a
b
le pipe length
Max. : 15m
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse modulating
valve at liquid side
(SEV15RC2)
valve at liquid side
(SEV15RC2)
Ø1,5 x 200
Ø1,5 x 200
TD
4-way valve
(CHV-0213)
(CHV-0213)
Compressor
DA91A1F-44F
DA91A1F-44F
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Propeller fan
Refrigerant amount : 0,8kg
OUTDOOR UNIT
Muffler
Muffler
TE
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
RAS-10YKV-E/RAS-10YAV-E
RAS-13YKV-E/RAS-13YAV-E
RAS-13YKV-E/RAS-13YAV-E