(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
For the above example, perform setting by 
connecting singly the wired remote controller 
without remote controller inter-unit cable.
Group address
 Individual : 
0000
 Master 
unit 
0001
  Sub unit 
: 0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address 
 1
Indoor unit address 
 1
Group address 
 1
1
2
2
2
1
2
2
2
2
<Operation procedure>
1    2    3    4    5    6    7    8    9    10    11  
END
1
3, 6, 9  
END
 11
2, 5, 8
4, 7, 10   
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
13-4. Address Setup 
(Manual setting from remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push 
SET
 + 
CL
 + 
TEST
 buttons simultaneously
for 4 seconds or more.
2
(
 Line address)
Using the temperature setup 
 / 
 buttons,
set 
12 
 to the item code.
3
Using timer time 
 / 
 buttons, set the line address.
4
Push 
SET
 button. (OK when display goes on.)
5
(
 Indoor unit address)
Using the temperature setup 
 / 
 buttons, set 
13 
 to the item code.
6
Using timer time 
 / 
 buttons, set 1 to the line address.
7
Push 
SET
 button. (OK when display goes on.)
8
(
 Group address)
Using the temperature setup 
 / 
 buttons, set 
14 
 to the item code.
9
Using timer time 
 / 
 buttons, set 
0000 
to Individual, 
0001 
to Master unit, and 
0002 
to sub unit.
10
Push 
SET
 button. (OK when display goes on.)
11
Push 
TEST
 button.
Setup completes. (The status returns to the usual stop status.)