SELECTION OF INSTALLATION
Length of refrigerant pipe
connected to
indoor/outdoor unit
20m or shorter
*
21m to 30m
<SP560AT-E>
* Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds
20m, add 20g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 600g.)
20m, add 20g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 600g.)
Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.
cause a serious trouble of compressor.
<SP800AT-E>
* Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds
20m, add 20g/m of refrigerant and the maximum total
length of pipe is 30m.
(Max. amount of additional refrigerant is 200g.)
20m, add 20g/m of refrigerant and the maximum total
length of pipe is 30m.
(Max. amount of additional refrigerant is 200g.)
Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.
cause a serious trouble of compressor.
<SM800AT-E>
Length of refrigerant pipe
connected to
indoor/outdoor unit
20m or shorter
*
21m to 50m
Item
Addition of refrigerant is
unnecessary at the local site.
unnecessary at the local site.
<Addition of refrigerant>
Add 20g of refrigerant for every
1m of pipe which exceeds 20m.
Add 20g of refrigerant for every
1m of pipe which exceeds 20m.
CAUTION
<SP560AT-E, SP800AT-E only>
When using an air conditioner under low outside
temperature condition (Outside temp.:–5°C or
lower) with COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
temperature condition (Outside temp.:–5°C or
lower) with COOL mode, prepare a duct or wind
shield so that it is not affected by the wind.
<Example>
Item
Addition of refrigerant is
unnecessary at the local site.
unnecessary at the local site.
<Addition of refrigerant>
Add 20g of refrigerant for every
1m of pipe which exceeds 20m.
Add 20g of refrigerant for every
1m of pipe which exceeds 20m.
Length of refrigerant pipe
connected to
indoor/outdoor unit
20m or shorter
*
21m to 50m
Item
Addition of refrigerant is
unnecessary at the local site.
unnecessary at the local site.
<Addition of refrigerant>
Add 40g of refrigerant for every
1m of pipe which exceeds 20m.
Add 40g of refrigerant for every
1m of pipe which exceeds 20m.
* Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds
20m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 1200g.)
20m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 1200g.)
Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.
cause a serious trouble of compressor.
Length of refrigerant pipe
connected to
indoor/outdoor unit
30m or shorter
*
31m to 50m
Item
Addition of refrigerant is
unnecessary at the local site.
unnecessary at the local site.
<Addition of refrigerant>
Add 40g of refrigerant for every
1m of pipe which exceeds 30m.
Add 40g of refrigerant for every
1m of pipe which exceeds 30m.
* Caution at addition of refrigerant
When the total length of refrigerant pipe exceeds
30m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 800g.)
30m, add 40g/m of refrigerant and the maximum total
length of pipe is 50m.
(Max. amount of additional refrigerant is 800g.)
Charge the refrigerant accurately. Overcharge may
cause a serious trouble of compressor.
cause a serious trouble of compressor.
Air purge
• For air purge, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit for
air purge. (The refrigerant for air purge is not con-
tained in the outdoor unit.)
tained in the outdoor unit.)
Electrical cabling
• Be sure to fix the power cables and indoor/outdoor
connecting cables with clamps so that they do not
contact with the cabinet, etc.
contact with the cabinet, etc.
Before installation
Be careful to the following items before installation.
Length of refrigerant pipe
<SM560AT-E>
Discharge guide
Suction
Suction hood (Side)
Discharge hood
Discharge hood
Fin
Suction hood
(Rear side)
(Rear side)
Suction
Fin
Discharge