Check codes and parts to be checked
Wired 
remote 
control 
display
Wireless remote control
Sensor block display of 
receiving unit
Main defective parts
Judging 
device
Parts to be checked / error description
Air 
conditioner 
status
Indication
Operation Timer    Ready
 GR
GR  OR
Flashing
E01
No header remote 
control
Remote 
control
Incorrect remote control setting --- The header remote 
control has not been set (including two remote controls). 
*
Remote control 
communication error
No signal can be received from the indoor unit.
E02
Remote control 
transmission error
Remote 
control
System interconnection wires, indoor P.C. board, remote 
control 
--- No signal can be sent to the indoor unit.
*
E03
Indoor unit-remote 
control regular 
communication error 
Indoor
Remote control, network adapter, indoor P.C. board --- 
No data is received from the remote control or network 
adapter.
Auto-reset
E04
Indoor unit-outdoor 
unit serial 
communication error
Indoor
System interconnection  wires, indoor P.C. board, 
outdoor P.C. board --- Serial communication error 
between indoor unit and outdoor unit
Auto-reset
IPDU-CDB 
communication error
E08
Duplicated indoor 
addresses 
Indoor
Indoor address setting error --- The same address as the 
self-address was detected.
Auto-reset
E09
Duplicated header 
remote controls
Remote 
control
Remote control address setting error --- Two remote 
controls are set as header in the double-remote control 
control.
*
 (* The header indoor unit stops raising alarm and follower 
indoor units continue to operate.) 
E10
CPU-CPU 
communication error
Indoor
Indoor P.C. board --- Communication error between main 
MCU and motor microcomputer MCU
Auto-reset
E18
Header indoor unit-
indoor follower unit 
regular communication 
error
Indoor
Indoor P.C. board --- Regular communication is not 
possible between header and follower indoor units or 
between twin header (main) and follower (sub) units.
Auto-reset
E31
IPDU communication 
error
Outdoor
Communication error between IPDU and CDB
Entire stop
F01
ALT
Indoor unit heat 
exchanger sensor 
(TCJ) error
Indoor
Heat exchanger sensor (TCJ) , indoor P.C. board --- 
Open-circuit or short-circuit of the heat exchanger sensor 
(TCJ) was detected.
Auto-reset
F02
ALT
Indoor unit heat 
exchanger sensor (TC) 
error
Indoor
Heat exchanger sensor (TC), indoor P.C. board --- Open-
circuit or short-circuit of the heat exchanger sensor (TC) 
was detected.
Auto-reset
F04
ALT
Outdoor unit discharge 
temp. sensor  (TD) 
error
Outdoor
Outdoor temp. sensor (TD), outdoor P.C. board --- Open-
circuit or short-circuit of the discharge temp. sensor was 
detected.
Entire stop
F06
ALT
Outdoor unit temp. 
sensor (TE/TS) error
Outdoor
Outdoor temp. sensors (TE/TS), outdoor P.C. board --- 
Open-circuit or short-circuit of the heat exchanger temp. 
sensor was detected.
Entire stop
F07
(F06)
ALT
TL sensor error
Outdoor
TL sensor may be displaced, disconnected or short-
circuited.
Entire stop
F08
ALT
Outdoor unit outside 
air temp. sensor error
Outdoor
Outdoor temp. sensor (TO), outdoor P.C. board --- Open-
circuit or short-circuit of the outdoor air temp. sensor was 
detected.
Operation 
continued
F10
ALT
Indoor unit room temp. 
sensor (TA) error
Indoor
Room temp. sensor (TA), indoor P.C. board --- Open-
circuit or short-circuit of the room temp. sensor (TA) was 
detected.
Auto-reset
F12
(F06)
ALT
TS sensor error
Outdoor
TS sensor may be displaced, disconnected or short-
circuited.
Entire stop
F13
(L29)
ALT
Heat sink sensor error
Outdoor
Abnormal temperature was detected by the temp. sensor 
of the IGBT heat sink.
Entire stop
F15
(F06)
ALT
Temp. sensor 
connection error
Outdoor
Temp. sensor (TE/TS) may be connected incorrectly.
Entire stop
F29
SIM
Indoor unit, other P.C. 
board error
Indoor
Indoor P.C. board --- EEPROM error
Auto-reset
30-EN