Systematic diagram of refrigerating cycle
RAV-SM2244 series
Standard
Cooling
Overload
Low load
Standard
Heating
Overload
Low load
Pressure
(MPa)
(kg/cm²g)
Pd
Ps
Pd
Ps
3.14
0.88
32.0
  9.0
3.54
1.14
36.1
11.6
1.65
0.65
16.8
  6.6
2.60
0.67
26.5
  6.8
3.24
1.08
33.1
11.0
2.05
0.31
20.9
  3.2
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat
Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
84
14
10
37
88
17
16
46
41
  7
  5
  0
73
  2
42
  2
77
14
52
13
76
–12
34
–11
Compressor
drive revolution
frequency
(rps) 
64
62
36
66
36
75
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–15/–
20/–
7/6
30/–
24/18
15/–
–10/(70%)
This compressor has a 4-pole motor.
The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor
revolution number (rps).
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.
RAV-SM2804 series
Standard
Cooling
Overload
Low load
Standard
Heating
Overload
Low load
Pressure
(MPa)
(kg/cm²g)
Pd
Ps
Pd
Ps
3.15
0.79
32.1
  8.1
3.62
1.12
36.9
11.4
1.66
0.64
16.9
  6.5
2.85
0.63
29.1
  6.4
3.26
1.06
33.3
10.8
2.05
0.29
20.9
  3.0
Pipe surface temperature (°C)
Discharge
Suction
Indoor heat
Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
87
11
  9
41
89
18
16
48
42
  6
  5
  0
80
  1
47
  2
78
14
53
12
81
–13
33
–12
Compressor
drive revolution
frequency
(rps) 
80
64
36
80
36
96
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–15/–
20/–
7/6
30/–
24/18
15/–
–10/(70%)
This compressor has a 4-pole motor.
The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor
revolution number (rps).
This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe
length. Data will change depending on the mounted pipe length or combination with the indoor unit.