Справочник Пользователя для Toshiba RAV-SM452MUT-E

Скачать
Страница из 106
– 79 –
11-1-3. Monitor Function of Remote Controller Switch
n
Calling of sensor temperature display
<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor
mode from the remote controller.
<Operation procedure>
1    2    3    4
Returned to usual display
2
4
1
3
SET
TIME
TIMER SET
TEST
FILTER
LL
RESET
TEMP.
CL
FAN
SAVE
A
A
SWING/FIX
VENT
MODE
ON / OFF
UNIT  LOUVER
T
<Procedure>
1
Push  
TEST
 + 
CL
 buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is
displayed at first and then the temperature of item code 
00
  is
displayed.
ò
2
Push temperature set 
TEMP.
 buttons and then change
the item code of data to be monitored.
The item code list is shown below.
1  Only master unit in group control
ò
3
Push 
UNIT  LOUVER
 button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
ò
4
Pushing 
TEST
 button returns the status to the usual display.
1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd
seconds.
• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73]
are not displayed.
Indoor unit
data
Item code
00
01
02
03
04
Data name
Room temp. (control temp.) 
1
Room temp. (remote controller)
Room temp. (TA)
Heat exchanger temp. (TCJ)
Heat exchanger temp. (TC)
Outdoor unit
data
Item code
60
61
62
63
64
65
Data name
Heat exchanger temp. TE
Outside temp. TO
Discharge temp. TD
Suction temp. TS
Heat sink temp. THS