9-3. Error Mode Detected by LED on Outdoor P.C. Board
RAV-SP562AT-E only
<SW801: LED display in bit 1, bit 2 OFF>
• When multiple errors are detected, the latest error is displayed.
• When LED display is 
¡
 (Go on), there is the main cause of trouble on the objective part of control at CDB
side and the unit stops.
• When LED display is 
¥
 (Flash), there is the main cause of trouble on the objective part of control at IPDU
side and the unit stops.
• When case thermostat operates, the communication is interrupted on the serial circuit.
If continuing the case thermostat operation, a serial communication error occurs because serial sending to
the indoor unit is interrupted.
CDB side
IPDU side
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Item
TE sensor error
TD sensor error
TS sensor error
TO sensor error
Discharge temp. error
DC outdoor fan error
Communication error between IPDU
(Abnormal stop)
High-pressure release operation
EEPROM error
Communication error between IPDU
(No abnormal stop)
IGBT short-circuit protection
Detection circuit error
Current sensor error
Comp. lock error
Comp. breakdown
Check
code
Type A
F06
F04
F06
F08
P03
P22
L29
P04
P26
P29
H03
H02
H01
LED display
D800
D801
D802
D803
(Red)
(Yellow)
(Yellow)
(Yellow)
¡
l
l
l
¡
¡
l
l
l
l
¡
l
l
¡
l
l
l
¡
¡
l
¡
¡
¡
l
¡
l
l
¡
l
¡
l
¡
¡
¡
l
¡
l
l
¡
¡
¥
l
l
l
l
¥
l
l
¥
¥
l
l
l
l
¥
l
¥
l
¥
l
¡
 : Go on     
l
 : Go off      
¥
 : Flash (5Hz)
<<Check code>>
The check codes are classified into Type A and Type B according to the used remote controller.
Be sure to check the remote controller which you use.
Type A :
Neutral 2-cores type wired remote controller such as RBC-AMT31E, RBC-AMT32E, RBC-AS21E2,
and wireless remote controller kit such as TCB-AX21E2