ON-SITE SETTING AND OTHERS
3.1.7 Setting Addresses
Overview
To connect custom air conditioners to the TCC-LINK central control system for central control/monitoring,
addresses of connected indoor units must be set in the following procedure.
Connections/wiring
completed
System power ON
Auto address setting
The system performs automatically after power on.
Change refrigerant line address.
If auto address setting failed, set refrigerant line address manually.
* Refer to 
1
1
 ADDRESS SETTING.
Manual setting/change of refrigerant
line addresses
Is group control (including twin/triple/
double twin) going?
Re-set indoor units with central control function to header
unit, and other indoor units to follower unit.
NO
YES
NO
YES
Are all indoor units with central control
function header unit (group address=1)?
* Refer to 
1
1
 ADDRESS SETTING.
Central control address number
setting
* Refer to the manual of the central control system.
END
– 
67
 –