3.1.8 Central Control Address Number Setting
To connect an indoor unit to the central control remote controller, an address number for central control
must be set.
An address number for central control is indicated as the refrigerant line number of the remote
controller.
1.
   
Setting by Remote Controller on Indoor Unit Side
<Procedure> Perform the following steps in the operation OFF
mode.
1
Press 
 and 
 on the R/C simultaneously for 4 seconds
or more.
When group control is going, UNIT No. 
 is displayed first,
and all indoor units in the group are selected. At this time, the
fans of all the selected indoor units start running. (Fig. 1)
Maintain this state without pressing 
.
For individual remote controllers without group control, a
refrigerant line address and an indoor unit address are
indicated.
2
Specify code 
 with 
 buttons.
3
Choose setting data with 
 buttons.
Table 1 shows setting data.
4
Press 
 Indication on the LCD shows normal operation.
• To change an item for setting, return to 
2
.
5
Press 
 to return to the normal indication.
(Fig. 1)
Setting data
0001
0002
0003
0064
0099
.....
Address No. for central control
1
2
3
64
Not set (factory setting)
.....
Table 1
5
2
4
1
3
– 
70
 –