Operation procedure
End
1
2
2
1
Operation procedure
ADDRESS SETTING (Continued)
Checking location of indoor unit number
(1) To find the address of indoor unit whose location is clear
In case of independent operation (1:1 connection of wired R/C
and I/U)
Perform the procedure during operation of indoor unit.
<Procedure>
1
When the indoor unit is not working, press 
 on
the R/C.
2
Press 
.
UNIT No. 
 appears on the LCD and disappears in several
seconds.
The displayed number shows the refrigerant line address and
indoor unit address.
When other indoor units are connected to the same remote
controller (group control), their unit numbers are displayed in
order each time 
 is pressed.
(2) To find the location of indoor unit from its address
When checking indoor unit number in the group.
Perform the procedure while the indoor unit is not working.
This procedure stops operation of all indoor units in the group.
<Procedure>
Indoor unit numbers appear one by one and the fan and flap of
the displayed unit run.
1
Press 
 and 
 on the R/C simultaneously for 4 seconds
or more.
• UNIT No. 
 appears.
• The fan and flap of all indoor units in the group run.
2
Each pressing of 
 on the R/C displays unit numbers in
the group sequentially.
• The header unit address appears first.
• The fan and flap of a selected indoor unit run.
3
Press 
 to finish the procedure. Operation of all the indoor
units in the group turns OFF.
– 
75
 –