– 4 –
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. RAV-SM562XT-E / RAV-SM802XT-E
Indoor unit
Outdoor unit
TCJ 
sensor
Air heat exchanger
TC sensor
Refrigerant pipe 
at liquid side
Outer dia. 
B
Refrigerant pipe 
at gas side
Outer dia. 
A
Packed valve
Outer dia. 
B
Packed valve 
Outer dia. 
A
Max
30m
Cooling
Heating
Outer diameter of refrigerant pipe
Gas side   ∅A
Liquid side  ∅B
12.7 mm
6.4 mm
Model
562XT-E
RAV-SM
802XT-E
15.9 mm
9.5 mm
Note  : 
This Service Mamual describes explanation for the Under Ceiling 1 console type indoor unit.
For the combined outdoor unit, refer to the following Service Manual.
Outdoor unit Model name                  SVM to be referred
RAV-SMXX0AT-E                                    A03-007
RAV-SPXXXAT-E                              A03-014
RAV-SMXX1AT-E                              A05-001
RAV-SMXX2AT-E                              A05-018