(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Line address 
 1
Indoor unit address 
 1
Group address 
 1
For the above example, perform setting by connecting 
singly the wired remote controller without remote 
controller inter-unit cable.
Group address
Individual
: 0000
Master unit : 0001
Sub unit
: 0002
In case of group control
OUT
IN
OUT
IN
2
1
2
1    2    3    4    5    6    7    8    9    10    11
END
<Operation procedure>
1
3, 6, 9  
END
 11
2, 5, 8
4, 7, 10   
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
UNIT   No.
DATA
SET
R.C.
No.
13-3. Address Setup
In case that addresses of the indoor units will be determined prior to piping work after cabling work
(Manual setting from remote controller)
<Address setup procedure>
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push 
SET
 + 
CL
 + 
TEST
 buttons simultaneously
for 4 seconds or more.
2
(
 Line address)
Using the temperature setup 
 / 
 buttons,
set 
12 
 to the item code.
3
Using timer time 
 / 
 buttons, set the line address.
4
Push 
SET
 button. (OK when display goes on.)
5
(
 Indoor unit address)
Using the temperature setup 
 / 
 buttons,
set 
13 
 to the item code.
6
Using timer time 
 / 
 buttons, set 1 to the line address.
7
Push 
SET
 button. (OK when display goes on.)
8
(
 Group address)
Using the temperature setup 
 / 
 buttons,
set 
14 
 to the item code.
9
Using timer time 
 / 
 buttons, set 
0000 
 to Individual,
0001 
 to Master unit, and 
0002 
 to sub unit.
10
Push 
SET
 button. (OK when display goes on.)
11
Push 
TEST
 button.
Setup completes. (The status returns to the usual stop status.)