TROUBLESHOOTING
You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition 
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and error codes for various checks. Details of the error codes displayed on the wired remote 
controller of the indoor unit are described in the Installation Manual of the indoor unit.
Verifying Error code status (Outdoor control 
board)
1. Check that DIP switch SW803 is set to off.
2. Record the states (on or off) of LED 800 to LED 804 
(Display mode 1).
3. Press SW800 for at least 1 second. The LED status 
changes to display mode 2.
4. Since display mode 1 covers multiple errors with the 
same code display, mode 2 must also be used to 
determine the final error. Use the status recorded for 
LED 800 to LED 804 in display mode 1 (Item 2 
above) and combine it with the status for the same 
LED’s in display mode 2 (Item 3 above) to determine 
the complete error code using the chart below.
Verifying Error code status stored in 
memory (Outdoor control board)
1. Check that DIP switch SW803 is set to on.
2. Record the states (on or off) of LED 800 to LED 804 
(Display mode 1).
3. Press SW800 for at least 1 second. The LED status 
changes to display mode 2.
4. Since display mode 1 covers multiple errors with the 
same code display, mode 2 must also be used to 
determine the final error. Use the status recorded for 
LED 800 to LED 804 in display mode 1 (Item 2 
above) and combine it with the status for the same 
LED’s in display mode 2 (Item 3 above) to determine 
the complete error code using the chart below.
NOTE
An outside air temperature (TO) sensor error can be 
checked only when an error occurs.
No.
Cause
Display mode 1 
Display mode 2 
D800
D801
D802
D803
D804
D800
D801
D802
D803
D804
1
Normal
2
Discharge (TD) sensor error
{
{
{
3
Heat exchanger (TE) sensor error
{
{
{
4
Heat exchanger (TL) sensor error
{
{
{
5
Outside air temperature (TO) sensor error
{
{
{
6
Suction (TS) sensor error
{
{
{
7
Heat sink (TH) sensor error
{
{
{
8
Outdoor temperature sensor (TE/TS) connection 
error
{
{
{
9
Outdoor EEPROM error
{
{
{
10
Compressor lock
{
{
11
Compressor lock
{
{
12
Current detection circuit error
{
{
13
Thermostat for compressor activated
{
{
14
Model data not set 
(on the service P.C. board)
{
{
{
15
MCU-MCU communication error
{
{
{
16
Discharge temperature error
{
{
{
{
17
Abnormal power 
(open phase detected or abnormal voltage)
{
{
{
{
18
Heat sink overheat
{
{
{
{
19
Gas leak detected
{
{
{
{
20
4-way valve reverse error
{
{
{
{
21
High pressure release operation
{
{
{
{
20-EN