(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Line address 
 1
Indoor unit address 
 1
Group address 
 1
For the above example, perform setting by connecting 
singly the wired remote controller without remote 
controller inter-unit cable.
Group address
Individual
: 0000
Master unit : 0001
Sub unit
: 0002
In case of group control
OUT
IN
OUT
IN
2
1
2
1    2    3    4    5    6    7    8    9    10    11
END
<Operation procedure>
1
3, 6, 9  
END
 11
2, 5, 8
4, 7, 10   
ON / OFF
FAN
TEMP.
SWING/FIX
TIME
MODE
VENT
UNIT
SET
CL
FILTER
RESET TEST
TIMER SET
UNIT   No.
DATA
SET
R.C.
No.
13-3. Address Setup
In case th at addresses of th e indoor units will be determined prior to piping work  after cabling work
(Manual setting from remote controller)
<Address setup procedure>
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push  
SET
 + 
CL
 + 
TEST
 buttons simultaneously
for 4 seconds or more.
2
(
 Line address)
Using th e temperature setup 
 / 
 buttons,
set 
12 
 to th e item code.
3
Using timer time 
 / 
 buttons,  set th e line address.
4
Push  
SET
 button. (OK when display goes on.)
5
(
 Indoor unit address)
Using th e temperature setup 
 / 
 buttons,
set 
13 
 to th e item code.
6
Using timer time 
 / 
 buttons,  set 1 to th e line address.
7
Push  
SET
 button. (OK when display goes on.)
8
(
 Group address)
Using th e temperature setup 
 / 
 buttons,
set 
14 
 to th e item code.
9
Using timer time 
 / 
 buttons,  set 
0000 
 to Individual,
0001 
 to Master unit,  and 
0002 
 to sub unit.
10
Push  
SET
 button. (OK when display goes on.)
11
Push  
TEST
 button.
Setup completes. (The status returns to the usual stop status.)