Справочник Пользователя для Toshiba MMY-MAP1004HT8ZG-E
– 12 –
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
(7) Branching header
(4) Branching pipe
(5) Indoor unit connecting pipe
Indoor unit
First branch
Indoor unit
Header
unit A
Follower
unit D
Follower
unit C
Follower
unit B
(1) Outdoor unit connecting pipes
(8) Outdoor unit connection piping kit (For linking of outdoor units)
Y-shape
branching joint
Outdoor unit
(1)
(1)
(1)
(8)
(8)
(8)
(2)
(2) Balance pipes Ø9.5
(6)
(4)
(3) Main
piping
(6)
(6) Y-shaped branching joint
(5)
(5)
(5)
(5)
(4)
(6)
(6)
(6)
(4)
(4)
(4)
(5)
(5)
(5)
(5)
(5)
(2)
No.
Piping parts
Name
Selection of pipe size
Remarks
(1)
Outdoor unit
È
Outdoor unit
È
Outdoor unit
connection piping
kit
Outdoor unit
connecting pipe
Connecting pipe size of outdoor unit
Same as connecting
pipe size of the
outdoor unit.
(2)
Between Outdoor
unit connection
piping kits
Main connecting
piping between
outdoor units
Pipe size for connecting piping between outdoor units
Pipe size differs based
on the total capacity
code value of outdoor
units at the
downstream side.
(See Table 2.)
(3)
Outdoor unit
connection piping
kit of header unit
È
First branching
È
First branching
section
Main piping
Size of main piping
* Maximum equivalent length of main pipe is 70m or less (The actual
length is 50m or less.).
Pipe size differs based
on the capacity code
of the outdoor unit.
(See Table 2.)
(4)
Branching section
È
Branching section
È
Branching section
Branching pipe
Pipe size between branching sections *1
*1: If exceeding the main pipe size, set the size to the same as the
main pipe size.
Pipe size differs based
on the total capacity
code value of indoor
units at the
downstream side. If
the total value
exceeds the capacity
code of the outdoor
unit, apply the
capacity code of the
outdoor unit. (See
Table 1 and 2.)
Type
Gas side
Liquid side
MAP080
Ø22.2
Ø12.7
MAP100
Ø22.2
Ø12.7
MAP120
Ø28.6
Ø12.7
MAP140
Ø28.6
Ø15.9
MAP160
Ø28.6
Ø15.9
Total capacity codes of
outdoor units at the
downstream side
Gas
side
Liquid
side
Balanc
e pipe
Equivalent to
HP
Equivalent to
capacity
16 to below 22
45.0 to below
61.5
Ø28.6
Ø15.9
Ø9.5
22 to below 26
61.5 to below
73.0
Ø34.9
Ø19.1
26 to below 36
73.0 to below
101.0
Ø34.9
Ø19.1
36 or more
101.0 or more
Ø41.3
Ø22.2
Total capacity codes of all
outdoor units
Gas
side
Liquid
side
Equivalent to
HP
Equivalent to
capacity
8 to below 12
22.4 to below 33.5
Ø22.2
Ø12.7
12 to below 14
33.5 to below 38.4
Ø28.6
Ø12.7
14 to below 22
38.4 to below 61.5
Ø28.6
Ø15.9
22 to below 36
61.5 to below
101.0
Ø34.9
Ø19.1
36 to below 46
101.1 to below
130.0
Ø41.3
Ø22.2
46 or more
130.0 or more
* Ø41.3
Ø22.2
Total capacity codes of indoor
units at downstream side
Gas
side
Liquid
side
Equivalent to HP
Equivalent to
capacity
Below 2.4
Below 6.6
Ø12.7
Ø9.5
2.4 to below 6.4
6.6 to below 18.0
Ø15.9
Ø9.5
6.4 to below 12.2
18.0 to below 34.0
Ø22.2
Ø12.7
12.2 to below 20.2
34.0 to below 56.5
Ø28.6
Ø15.9
20.2 to below 35.2
56.5 to below 98.5
Ø34.9
Ø19.1
35.2 or more
98.5 ore more
Ø41.3
Ø22.2
23-EN