Справочник Пользователя для Toshiba MMY-MAP1004HT8ZG-E

Скачать
Страница из 34
– 22 –
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
„
Regulation of high frequency wave
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) 
at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the 
equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected 
only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be 
connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused 
from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the 
interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the 
interface point.
Ssc (*1)
Model
Ssc (kVA)
MMY-MAP0804HT8(Z)(ZG)-E
MMY-MAP0804T8(Z)(ZG)-E
1004
MMY-MAP1004HT8(Z)(ZG)-E
MMY-MAP1004T8(Z)(ZG)-E
1290
MMY-MAP1204HT8(Z)(ZG)-E
MMY-MAP1204T8(Z)(ZG)-E
1560
MMY-MAP1404HT8(Z)(ZG)-E
MMY-MAP1404T8(Z)(ZG)-E
1692
MMY-MAP1604HT8(Z)(ZG)-E
MMY-MAP1604T8(Z)(ZG)-E
1942
9
ADDRESS SETTING
On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.
CAUTION
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7-
segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a 
malfunction.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by 
turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
REQUIREMENT
• High voltage parts exist in the electrical control box. 
If you set addresses on an outdoor unit, operate the 
unit through the access door shown on the illustration 
on the right to avoid electric shock. Do not remove the 
cover of electrical control box. 
* After finishing operations, close the access door cover 
and fix it with the screw. 
„
Automatic address setting
Automatic addressing:
setting addresses using SW15 on the interface P.C. board on the header outdoor unit
Manual addressing:
setting addresses on the wired remote controller.
* When setting an address manually, the wired remote controller must temporarily be 
paired with an indoor unit one-to-one. (when the system is organized for group 
operation and no Remote controller)
No central control:
Central control of 2 or more refrigerant lines:
(Example)
When controlling a single refrigerant line 
centrally
When controlling 2 or more refrigerant lines 
centrally
Address setting 
procedure
To procedure 1
To procedure 2
System wiring 
diagram
Access 
door cover
Fixing screw for the 
access door cover
Cover of the electrical 
control box
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central 
remote 
controller
Central 
remote 
controller
Remote 
controller
Remote 
controller
Remote 
controller
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central 
remote 
controller
Remote 
controller
Remote 
controller
Remote 
controller
43-EN
44-EN
+00EH99871699_01EN.book  Page 22  Thursday, August 26, 2010  4:41 PM