Справочник Пользователя для Toshiba MMY-MAP1004HT8ZG-E

Скачать
Страница из 34
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
– 28 –
3
Push the 
 button.
• The address of one of the indoor units 
connected to the selected refrigerant line is 
indicated on the LCD display and the fan and 
louvers of the unit are activated.
At first, the current indoor unit address is 
displayed in 
SET DATA
.
(No system address is indicated.)
4
Push the TIME 
 / 
 buttons repeatedly to 
change the value of the indoor unit address 
in SET DATA.
Change the value in SET DATA to that of a 
new address. 
5
Push the 
 button to confirm the new 
address on SET DATA. 
6
Push the 
 button (left side of the 
button) repeatedly to select another address 
to change. Each time you push the button, 
the indoor unit numbers in a refrigerant line 
are indicated one after another. Only the fan 
and louvers of the selected indoor unit are 
activated. 
Repeat steps 
4
 to 
6
 to change the indoor unit 
addresses so as to make each of them unique.
7
Push the 
 button.
(All the segments on the LCD display light up.)
8
Push the 
 button to finish the procedure.
„
Resetting the address
(Resetting to the factory 
default (address undecided))
Method 1
Clearing each address separately using a wired remote 
controller.
Set the system address, indoor unit address and group 
address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting 
procedures using the wired remote controller on the previous 
pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at 
once from the outdoor unit.
1
Turn off the refrigerant line to reset to the 
factory default and set the header outdoor 
unit of the line as below.
1) Disconnect the relay connectors between the 
[U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already 
been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface 
P.C. board of the header outdoor unit if the 
switch is OFF.
(Leave it as it is if it has already been set to 
ON.)
SET
4
8
5, 7 
6
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
Press to finish 
setting.
Finish
SET
SET
TEST
2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the 
addresses. About one minute after turning on the power, confirm that the 7-segment display on 
the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header 
outdoor unit of the refrigerant line as follows.
3
Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1 
respectively.
4
After a time “U.1.L08” appears on the 7-segment display if the address clearing has been 
completed successfully.
If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other 
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5
Set the addresses again after finishing the clearance.
SW01
SW02
SW03
SW04
Clearable addresses
2
1
2
Confirm that the 7-segment display indicates 
“A.d.buS” and turn SW04 ON for more than five 
seconds.
System/indoor unit/group address
2
2
2
Confirm that the 7-segment display indicates 
“A.d.nEt” and turn SW04 ON for more than five 
seconds.
Central control address
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A B
Central control 
controller
Header 
unit
Follower unit
Follower unit
Remote 
controller
Remote 
controller
Remote 
controller
Remote 
controller
Indoor units to have their addresses initialized
Header 
unit
Header 
unit
55-EN