– 8 –
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
• Anchor bolt positions are as shown below:
(Unit: mm)
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
Model type
A
B
MAP080*, MAP1000*, MAP120*
700
990
MAP1404*, 1604*
920
1210
2. When drawing out the refrigerant pipe from the 
underside, set the height of the stand to 500mm or 
more.
3. Do not use 4 stands on the corner to support the 
outdoor unit.
A
A
A
B
755
790
Continuous hole
(15 x 20 long hole)
310 or 
more
310 or 
more
50
0mm
 o
mor
e
NO GOOD
GOOD
GOOD
GOOD
NO GOOD
NO GOOD
NO GOOD
Anchor bolt
Vibration-proof rubber
Install the vibration-proof 
rubber so that the bent part 
of the fixing leg is 
grounded.
The bent part of the 
fixing leg is not 
grounded.
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of 
capacity from the one with the largest capacity. (A (Header unit) 
≥ B ≥ C ≥ D)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1 and 3)
• Be sure to use a T-shaped branch joint (RBM-BT14E/RBM-BT24E: separately purchased) to connect each 
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a 
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into 
the header unit.)
Liquid piping
Gas piping
• When attaching a Y-shaped branch unit for the gas side, attach it level with the ground (Be sure not to exceed 
±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
▼ Figure 1
▼ Figure 2
[Inverse connection of a gas-side branch unit]
▼ Figure 3
▼ Figure 4
GOOD
Header unit 
A
Follower unit 
B
Follower unit 
C
Main pipe
To the indoor unit
NO GOOD
Header unit 
A
Follower unit 
B
Follower unit 
C
Main pipe
To the indoor unit
NO GOOD
GOOD
Header unit 
A
Follower unit 
B
Follower unit 
C
Main pipe
To the indoor unit
Extension valve
NO GOOD
Header unit 
A
Follower unit 
B
Follower unit 
C
To gas-side branch 
unit
Main pipe
To the indoor unit
A
B
Within ±15 degrees
(Horizontal line)
Within ±15 
degrees
(Horizontal line)
(A arrow view)
At a level position
(B arrow view)
Do not connect 
a branch unit 
vertically.
15-EN
16-EN
+00EH99871699_01EN.book  Page 8  Thursday, August 26, 2010  4:41 PM