Adding refrigerant 
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant. 
Calculation of additional refrigerant charge amount 
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional 
refrigerant.
Table 1
Heat pump 
type
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Charging amount (kg)
11.5
Cooling only 
type
Outdoor unit type
MAP080
MAP100
MAP120
MAP140
MAP160
Charging amount (kg)
10.5
10.5
10.5
11.5
11.5
Additional refrigerant charge 
amount at local site
=
Real length of liquid pipe
×
Additional refrigerant charge 
amount per 1m liquid pipe 
(Table 1)
+
Corrective amount of refrigerant 
depending on HP of co-
operating outdoor units 
(Table 2)
Liquid pipe dia. (mm)
6.4
9.5
12.7
15.9
19.1
22.2
Additional refrigerant amount/1m liquid 
pipe (kg/m)
0.025
0.055
0.105
0.160
0.250
0.350
Table 2
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the 
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and 
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas 
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Combined HP (HP)
Combined outdoor units (HP)
C (Corrective amount 
of refrigerant) (kg)
Standard type
8
8HP
1.5
10
10HP
2.5
12
12HP
3.5
14
14HP
8.5
16
16HP
10.5
18
10HP
8HP
0.0
20
10HP
10HP
3.0
22
12HP
10HP
5.0
24
12HP
12HP
7.5
26
16HP
10HP
8.5
28
16HP
12HP
9.5
30
16HP
14HP
11.5
32
16HP
16HP
12.5
34
12HP
12HP
10HP
3.0
36
12HP
12HP
12HP
4.0
38
16HP
12HP
10HP
6.0
40
16HP
12HP
12HP
7.0
42
16HP
14HP
12HP
8.0
44
16HP
16HP
12HP
10.0
46
16HP
16HP
14HP
12.0
48
16HP
16HP
16HP
14.0
High Efficiency type
16
8HP
8HP
0.0
24
8HP
8HP
8HP
-4.0
26
10HP
8HP
8HP
-4.0
28
10HP
10HP
8HP
-2.0
30
10HP
10HP
10HP
0.0
32
8HP
8HP
8HP
8HP
-6.0
34
10HP
8HP
8HP
8HP
-6.0
36
10HP
10HP
8HP
8HP
-6.0
38
10HP
10HP
10HP
8HP
-6.0
40
10HP
10HP
10HP
10HP
-5.0
42
12HP
10HP
10HP
10HP
-4.0
44
12HP
12HP
10HP
10HP
-2.0
46
12HP
12HP
12HP
10HP
0.0
48
12HP
12HP
12HP
12HP
2.0 
31-EN
32-EN
+00EH99871699_01EN.book  Page 16  Thursday, August 26, 2010  4:41 PM