SMMS-i
Installation Manual
SMMS-i
Installation Manual
– 27 –
refrigerant lines are interconnected for central 
control) 
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the 
indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of 
the refrigerant line of the selected unit are indicated one after 
another and the fan and louvers of the indicated indoor units 
are activated.
1
Push and hold the TIME 
 and 
 buttons 
at the same time for more than 4 seconds.
At first, the line 1 and CODE No. 
 
(Address Change) are indicated on the LCD 
display. (Select an outdoor unit.) 
2
Push the 
 (left side of the button) and 
 buttons repeatedly to select a system 
address.
3
Push the 
 button to confirm the system 
address selection.
• The address of an indoor unit connected to the 
selected refrigerant line is indicated on the LCD 
display and its fan and louvers are activated. 
4
Push the 
button (left side of the 
button). Each time you push the button, the 
indoor unit numbers of the selected 
refrigerant line are indicated one after 
another.
• Only the fan and louvers of the indicated indoor 
unit are activated.
To select another system address
5
Push the 
 CL button to return to step 
2
.
• After returning to step 
2
, select another system 
address and check the indoor unit addresses of 
the line.
6
Push the 
 button to finish the procedure.
„
Changing the indoor unit 
address using a remote 
controller
To change an indoor unit address using a 
wired remote controller.
▼ The method to change the address of an 
individual indoor unit (the indoor unit is paired 
with a wired remote controller one-to-one), or 
an indoor unit in a group.
(The method is available when the addresses 
have already been set automatically.)
(Execute it while the units are stopped.)
1
Push and hold the 
, and 
 buttons at 
the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, 
the first indicated UNIT No. is that of the head 
unit.)
2
Push the 
 button (left side of the 
button) repeatedly to select an indoor unit 
number to change if 2 or more units are 
controlled in a group. (The fan and louvers 
of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3
Push the TEMP. 
 / 
 buttons 
repeatedly to select 
 for CODE No..
4
Push the TIME 
 / 
 buttons repeatedly to 
change the value indicated in the SET DATA 
section to that you want.
5
Push the 
 button.
5
6
1
3
4
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
TEST
SWING/FIX
SET
CL
TEST
3
5
8
1
4
2, 6, 7
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
Finish
SET
CL
TEST
SET
6
Push the 
 button (left side of the 
button) repeatedly to select another indoor 
UNIT No. to change.
Repeat steps 
4
 to 
6
 to change the indoor unit 
addresses so as to make each of them unique.
7
Push the 
 button (left side of the 
button) to check the changed addresses.
8
If the addresses have been changed 
correctly, push the 
 button to finish the 
procedure.
▼ To change all the indoor unit addresses using 
an arbitrary wired remote controller.
(The method is available when the addresses 
have already been set automatically.)
(When communication wirings of 2 or more 
refrigerant lines are interconnected for central 
control) 
NOTE
You can change the addresses of indoor units in each 
refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change 
the addresses. 
If no number appears on UNIT No., no outdoor unit exists on 
the line. Push 
 button and select another line following 
step 
2
(Execute it while the units are stopped.)
1
Push and hold the TIME 
 / 
 buttons at 
the same time for more than 4 seconds.
At first, the line 1 and CODE No. 
 
(Address Change) are indicated on the LCD 
display.
2
Push 
 (left side of the button) and 
 buttons repeatedly to select a system 
address.
TEST
3
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
Cancels the line selection
CL
SWING/FIX
53-EN
54-EN
+00EH99871699_01EN.book  Page 27  Thursday, August 26, 2010  4:41 PM