Remote controller wiring
• Strip off approx. 14mm cover of the wire to be connected.
• Twist wire of the remote controller to be connected with wire of the remote controller unit (or sensor), and press-fit
them with a wire joint. (Wire joints (White: 2 pieces) are included in the accessory of the main remote controller
(sold separately) or wireless remote controller kit (sold separately).)
• As the remote controller wire has no polarity, there is no problem if connections to indoor unit terminal blocks A
and B are reversed.
<Wiring diagram>
Wiring between indoor and outdoor units
NOTE
An outdoor unit connected
with indoor/outdoor inter-unit
wire becomes automatically
the header unit.
Address setup
Set up the addresses according to the Installation Manual attached to the outdoor unit.
Wiring on the ceiling panel
According to the Installation Manual of the ceiling panel, connect the connector.
Terminal block 
for remote controller 
wiring of indoor unit
A
B
Approx. 200mm
W : White
B : Black
W
B
Remote controller wire 
(Local procure)
Wire from remote controller unit 
or sensor
Connecting 
part
Remote 
controller unit 
or sensor part
Wire from remote 
controller or sensor
Remote controller wiring
Wire joint
Header unit
Follower unit
Earth leakage breaker
Earth leakage breaker
Switch
(Earth)
(Open)
Earth 
Outdoor power supply
3-phase 
  380–415V, 50Hz
  380V, 60Hz
Central control line wire
Power supply 
  220–240V 
~
  50Hz
  220V 
~
  60Hz
Remote controller, 
for central control, etc.
Connection of shield 
wire closed terminal
Inter-unit wire between outdoor units
Indoor/Outdoor inter-unit wire
Indoor power supply
  220–240V 
~
  50Hz
  220V 
~
  60Hz
(Earth)
Connection of shield 
wire closed terminal
(Remote controller group operation)
Pull box
Indoor unit