Coupling size of brazed pipe
(Unit: mm)
„
Selection of pipe size
Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable 
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs 
based on the height difference between the indoor units.
• When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent 
to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15m: Up to 105% of the capacity code
Connected section
External size
Internal size
Standard outer dia. 
of connected 
copper pipe
Connected section
Min. thickness 
of coupling
External size
Internal size
Min. depth of 
insertion
Oval value
 Standard outer dia. 
(Allowable difference)
C
F
K
G
6.35
6.35 (±0.03)
6.45 (
)
7
6
0.06 or less
0.50
9.52
9.52 (±0.03)
9.62 (
)
8
7
0.08 or less
0.60
12.70
12.70 (±0.03)
12.81 (
)
9
8
0.10 or less
0.70
15.88
15.88 (±0.03)
16.00 (
)
9
8
0.13 or less
0.80
19.05
19.05 (±0.03)
19.19 (
)
11
10
0.15 or less
0.80
22.22
22.22 (±0.03)
22.36 (
)
11
10
0.16 or less
0.82
28.58
28.58 (±0.04)
28.75 (
)
13
12
0.20 or less
1.00
34.92
34.90 (±0.04)
35.11 (
)
14
13
0.25 or less
1.20
38.10
38.10 (±0.05)
38.31 (
)
15
14
0.27 or less
1.26
41.28
41.28 (±0.05)
41.50 (
)
15
14
0.28 or less
1.35
K
ØC
G
ØF
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
Table 1
Table 2
* For combination of the outdoor units, refer to “Combination of outdoor units”.
Indoor unit 
capacity rank
Capacity code
Equivalent to HP
Equivalent to 
capacity
007
0.8
2.2
009
1
2.8
012
1.25
3.6
015
1.7
4.5
018
2
5.6
024
2.5
7.1
027
3
8
030
3.2
9
036
4
11.2
048
5
14
056
6
16
072
8
22.4
096
10
28
Outdoor unit 
model name
(Standard model)
Capacity code
No. of 
indoor 
units
Outdoor unit 
model name
(High Efficiency 
model)
Capacity code
No. of 
indoor 
units
Equivalent to 
HP
Equivalent to 
capacity
Equivalent to 
HP
Equivalent to 
capacity
MMY-MAP0804
8
22.4
13
MMY-MAP1004
10
28
16
MMY-MAP1204
12
33.5
20
MMY-MAP1404
14
40
23
MMY-MAP1604
16
45
27
MMY-AP1624
16
45
27
MMY-AP1814
18
50.4
30
MMY-AP2014
20
56
33
MMY-AP2214
22
61.5
37
MMY-AP2414
24
68
40
MMY-AP2424
24
68
40
MMY-AP2614
26
73
43
MMY-AP2624
26
73
43
MMY-AP2814
28
78.5
47
MMY-AP2824
28
78.5
47
MMY-AP3014
30
85
48
MMY-AP3024
30
85
48
MMY-AP3214
32
90
48
MMY-AP3224
32
90
48
MMY-AP3414
34
96
48
MMY-AP3424
34
96
48
MMY-AP3614
36
101
48
MMY-AP3624
36
101
48
MMY-AP3814
38
106.5
48
MMY-AP3824
38
106.5
48
MMY-AP4014
40
112
48
MMY-AP4024
40
112
48
MMY-AP4214
42
118
48
MMY-AP4224
42
118
48
MMY-AP4414
44
123
48
MMY-AP4424
44
123
48
MMY-AP4614
46
130
48
MMY-AP4624
46
130
48
MMY-AP4814
48
135
48
MMY-AP4824
48
135
48
21-EN
22-EN