Be sure to keep the rule of below tables about size and length of communication wiring.
 (*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
Table-1
Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring 
(L4)
Wiring
2-core, non-polarity
Type
Shield wire
Size/Length
1.25 mm
2
: Up to 1000 m/2.0 mm
2
: Up to 2000 m (*1)
Table-2
Communication wiring between outdoor units (L5)
Wiring
2-core, non-polarity
Type
Shield wire
Size/Length
1.25 mm
2
 to 2.0 mm
2
/Up to 100 m (L5)
Table-3
Remote controller wiring (L6, L7)
Wire
2-core, non-polarity
Size
0.5 mm
2
 to 2.0 mm
2
 
Length
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
U1 U2
A B
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2 U5 U6
L1
L5
L6
L7
L4
L2
L3
Header
unit
Header 
unit
Follower 
unit
Follower 
unit
Follower 
unit
Header 
unit
Follower 
unit
Super modular multi system
Central 
control 
controller
Outdoor unit
Indoor unit
Table-1
Table-2
Table-1
Remote controller
Remote controller
Remote controller
Table-3
Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
„
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and 
communication wires through the holes.
NOTE
Be sure to separate the power wire and communication wires.
A B
A B
A B
A B
A B
A B
(A.B)
Remote controller
Indoor unit
No.1
No.2
No.3
No.4
No.7
No.8
Piping/wiring panel
Knockout for the power 
supply wire
Knockout for the power 
wire
Knockout for the
communication wire
39-EN
40-EN
+00EH99871699_01EN.book  Page 20  Thursday, August 26, 2010  4:41 PM