Справочник Пользователя для Toshiba MMY-MAP1004HT8-E

Скачать
Страница из 34
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
– 26 –
<Line (system) address>
2
Push the TEMP. 
 / 
 buttons 
repeatedly to set the CODE No. to 
.
3
Push the TIME 
 / 
 buttons repeatedly to 
set a system address.
(Match the address with the address on the 
interface P.C. board of the header outdoor unit in 
the same refrigerant line.)
4
Push  
button.
(It is OK if the display turns on.)
<Indoor unit address>
5
Push the TEMP. 
 / 
 buttons 
repeatedly to set the CODE No. to 
.
6
Push the TIME 
 / 
 buttons repeatedly to 
set an indoor unit address.
7
Push the 
 button.
(It is OK if the display turns on.)
<Group address>
8
Push the TEMP. 
 / 
 buttons 
repeatedly to set the CODE No. to 
.
9
Push the TIME 
 / 
 buttons repeatedly to 
set a group address. If the indoor unit is 
individual, set the address to 
; header 
unit, ; 
follower 
unit, .
10
Push the 
 button.
(It is OK if the display turns on.)
11
Push the 
 button.
The address setting is complete.
(
 flashes. You can control the unit after 
 
has disappeared.)
NOTE
1. Do not use address numbers 29 or 30 when setting 
system addresses using the remote controller.
These 2 address numbers cannot be used on 
outdoor units and the CODE No. [E04] (Indoor/
outdoor communication error) will appear if they are 
mistakenly used.
2. If you set addresses to indoor units in 2 or more 
refrigerate lines manually using the remote 
controller and will control them centrally, set the 
header outdoor unit of each line as below.
• Set a system address for the header outdoor unit 
of each line with SW13 and 14 of their interface 
P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C. 
boards of all the header outdoor units connected 
to the same central control, except the unit that 
has the lowest address. (For unifying the 
termination of the wiring for the central control of 
indoor and outdoor units)
• Connect the relay connectors between the [U1, 
U2] and [U3, U4] terminals on the header outdoor 
unit of each refrigerate line.
• After finishing all the settings above, set the 
address of the central control devices. (For the 
setting of the central control address, refer to the 
installation manuals of the central control 
devices.)
Individual
 : 0000
Header unit
 : 0001
In case of group 
control
Follower unit
 : 0002
SET
SET
}}
SET
TEST
SETTING
SETTING
„
Confirming the indoor unit 
addresses and the position of 
an indoor unit using the 
remote controller
Confirming the numbers and 
positions of indoor units
To see the indoor unit address of an 
indoor unit which you know the position of
▼ When the unit is individual (the indoor unit is 
paired with a wired remote controller one-to-
one), or it is a group-controlled one.
(Execute it while the units are running.)
1
Push the 
 button if the units stop.
2
Push the 
 button (left side of the 
button).
A unit numbers 
 is indicated on the LCD (it will 
disappear after a few seconds). The indicated 
number shows the system address and indoor unit 
address of the unit. 
When 2 or more indoor units are connected to the 
remote controller (group-controlled units), a 
number of other connected units appears each 
time you push the 
 button (left side of the 
button).
To find an indoor unit’s position from its 
address
▼ When checking unit numbers controlled as a 
group
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after 
another. The fan and louvers of the indicated units are 
activated.
1
Push and hold the 
 and 
 buttons at 
the same time for more than 4 seconds.
 appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the 
group are activated.
2
Push the 
 button (left side of the 
button). Each time you push the button, the 
indoor unit numbers are indicated one after 
another.
• The first-indicated unit number is the address of 
the header unit.
• Only the fan and louvers of the indicated indoor 
unit are activated.
3
Push the 
 button to finish the procedure.
All the indoor units in the group stop.
▼ To check all the indoor unit addresses using 
an arbitrary wired remote controller.
(When communication wirings of 2 or more 
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
Starts 
running
ON / OFF
3
1
2
1
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
Stop
VENT
TEST
TEST
51-EN
52-EN
+00EH99871699_01EN.book  Page 26  Thursday, August 26, 2010  4:41 PM