<Corrective trial>
▼ Start operation
1
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
2
Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
▼ Stop operation
1
Set the rotary switches on the interface P.C. board of the header unit back: 
SW01 to [1], SW02 to [1] and SW03 to [1].
[A]
[C    ]
[H    ]
[B]
[            ]
[            ]
7-segment display
[A]
[C    ]
[H    ]
[B]
[    -  C    ]
[    -  H    ]
7-segment display
[A]
[U1]
[B]
[         ]
7-segment display
SW04
SW01 SW02 SW03