TROUBLESHOOTING
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by 
checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary 
code for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Rotary switch setting value
Indication
LED
SW01
SW02
SW03
1
1
1
Outdoor unit check code
A
Outdoor unit number
(U
1
 to U
4
)
B
Check code display*
Check code
Check code name
Indication on 7-segment display on the outdoor unit
Auxiliary code
E06
Number of indoor units which received normally
Decrease of number of indoor units
E07
Indoor/outdoor communication circuit error
E08
Duplicated indoor addresses
Duplication of indoor addresses.
E12
01: Communication between indoor and outdoor units
02: Communication between outdoor units
Automatic addressing start error
E15
No indoor unit during automatic addressing
E16
00: Capacity over
01~: Number of connected units
Capacity over / number of connected indoor units
E19
00: Header is nothing
02: 2 or more header units
Number of header outdoor unit error
E20
01: Other line indoor connected
02: Other line indoor connected
Other lines connected during automatic addressing
E23
Sending error between outdoor units communication
E25
Duplicated follower outdoor address set up
E26
Number of outdoor units which received normally
Decrease of connected outdoor units
E28
Detected outdoor
Follower outdoor unit error
E31
IPDU quantity information
(*1)
IPDU communication error
F04
TD1 sensor error
F05
TD2 sensor error
F06
01: TE1 sensor
02: TE2 sensor
TE1 sensor error
TE2 sensor error
F07
TL sensor error
F08
TO sensor error
F12
TS1 sensor error
F13
01: Compressor 1
02: Compressor 2
03: Compressor 3
TH (Heat sink) sensor error
D600
A
B
D601 D602 D603 D604
F15
Outdoor temp. sensor miswiring
Outdoor pressure sensor miswiring (TE1, TL)
F16
Outdoor temp. sensor miswiring
Outdoor pressure sensor miswiring (Pd, Ps)
F22
TD3 sensor error
F23
Ps sensor error
F24
Pd sensor error
F31
Outdoor EEPROM error
H01
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor breaking down
H02
01: Compressor 1
02: Compressor 2
03: Compressor 3
Compressor error (Locked)
H03
01: Compressor 1
02: Compressor 2
03: Compressor 3
Current detection circuit error
H05
TD1 sensor miswiring
H06
Low pressure proctive operation
H07
Oil level down detection
H08
01: TK1 sensor error 
02: TK2 sensor error
03: TK3 sensor error 
04: TK4 sensor error
05: TK5 sensor error
Temperature sensor error for oil level
H15
TD2 sensor miswiring
H16
01: TK1 oil circuit error
02: TK2 oil circuit error
03: TK3 oil circuit error
04: TK4 oil circuit error
05: TK5 oil circuit error
Oil level detector circuit error
H25
TD3 sensor miswiring
L04
Outdoor system address duplication
L06
Number of prior indoor units
Duplication of indoor units with priority
L08
Indoor unit group/address unset
L10
Outdoor unit capacity unset. 
L17
Mismatch of the outdoor unit model
L28
Outdoor connected quantity over
L29
IPDU number information
(*1)
IPDU quantity error
L30
Detected indoor unit address
External interlock of indoor unit
L31
Other compressor errors
P03
Discharge temperature TD1 error
P04
01: Compressor 1
02: Compressor 2
03: Compressor 3
High-pressure SW system operation
P05
00: 
Phase missing/power failure detection
01: Compressor 1
02: Compressor 2
03: Compressor 3
Inverter DC voltage error (on compressor)
Check code
Check code name
Indication on 7-segment display on the outdoor unit
Auxiliary code
61-EN