– 9 –
SMMS-i
Installation Manual
SMMS-i
Installation Manual
When drawing pipes downward
• Adding only one follower unit is possible. Install the additional unit so that its position is opposite to the header 
unit. Use an extension valve for installation (See the figure above.).
Specify the pipe diameter in advance to allow for adding another unit.
[Vertical connection of branch units]
▼ Figure 5
▼ Figure 6
GOOD
Header unit 
A
Follower unit 
B
Follower unit 
C
L-shaped
pipe
To gas-side branch 
unit
To gas-side branch 
unit
NO GOOD
To gas-side
branch unit
To gas-side
branch unit
7
REFRIGERANT PIPING
WARNING
• If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
• After installation, check that the refrigerant gas does not leak.
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range, 
noxious gas may be generated.
„
Connection of refrigerant pipe
• The refrigerant pipe connecting section is set in the 
outdoor unit. Remove the front panel and the piping/
wiring panel. (M5: 9 pcs.) 
• As shown in the illustration on the right, the hooks are 
at the right and left sides of the front panel. Lift up and 
remove the front panel.
• Pipes can be drawn out forward or downward from the 
outdoor unit.
• When drawing out the pipe forward, draw it out to the 
outside via the piping/wiring panel, and leave a space 
of 500mm or more from the main pipe connecting the 
outdoor unit with the indoor unit, considering service 
work or other work on the unit. (For replacing the 
compressor, 500mm or more space is required.)
• When drawing out the pipe downward, remove the 
knockouts on the base plate of the outdoor unit, draw 
the pipes out of the outdoor unit, and perform piping on 
the right/left or rear side. Downward length of the balance pipe should be 5m or less.
(MAP080, MAP100, MAP120)
(MAP140, MAP160)
Front panel
Piping/wiring panel
(Rear piping)
Drawing out 
downward
(Left piping)
(Right piping)
Drawing out forward
50
0m
m
 o
m
or
e
Hook
(Left 
piping)
(Right 
piping)
Ball valve of gas 
side
Packed valve of liquid 
side
Packed valve of 
balance pipe
Ball valve of gas 
side
Ball valve of liquid 
side
Packed valve of 
balance pipe
17-EN
18-EN