Справочник Пользователя для Toshiba MMY-MAP1204HT8Z-E

Скачать
Страница из 34
– 18 –
SMMS-i
Installation Manual
EN
SMMS-i
Installation Manual
Pipe holding bracket
Attach pipe holding brackets following the table below.
When using the piping cover
When not using the piping cover
Diameter of pipe (mm)
Interval
Ø15.9 - Ø19.1
2m
Ø22.2 - Ø41.3
3m
Piping/wiring panel
Drawing-out sideward
Close the opening with the 
pipe cover.
Drawing-out 
frontward
Drawing-out 
downward
Piping/wiring panel
Drawing-out sideward
Fill silicon or putty into the 
periphery of the pipes.
Drawing-out 
frontward
Drawing-out 
downward
8
ELECTRIC WIRING
WARNING
The appliance shall be installed in accordance with national wiring regulations. 
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
CAUTION
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise, 
the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the 
coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the 
installation manual of each indoor unit.
„
Power supply specifications
Power wiring selection
Standard model
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Do not bridge the power between outdoor units 
through the equipped terminal blocks (L
1
, L
2
, L
3
N). 
Model
Power Supply
MCA
(A)
MOCP
(A)
Phase and frequency
Nominal Voltage
MMY-MAP0804*
MMY-MAP1004*
MMY-MAP1204*
MMY-MAP1404*
MMY-MAP1604*
3N~ 50Hz
380-400-415V
23.5
25.5
28.5
33.2
36.5
32
32
40
40
50
MMY-AP1814*
MMY-AP2014*
MMY-AP2214*
MMY-AP2414*
MMY-AP2614*
MMY-AP2814*
MMY-AP3014*
MMY-AP3214*
3N~ 50Hz
380-400-415V
49.0
51.0
54.0
57.0
62.0
65.0
69.7
73.0
63
63
63
63
80
80
80
100
Power supply for
outdoor units
NO GOOD
35-EN