Switch setting (setting example when 
controlling 2 or more refrigerant lines 
centrally)
Outdoor units (setting manually)
*The items in bold font must be set manually.
Outdoor unit’s interface 
P.C. board
Header unit
Follower unit
Header unit
Follower unit
Header unit
Factory default
SW13, 14
(Line (system) address)
1
(No setting 
required)
2
(No setting 
required)
3
1
Dip switch 2 of SW30
(Terminator of indoor/
outdoor communication 
line and central control 
line)
ON
(No setting 
required)
Set to OFF 
after setting 
addresses.
(No setting 
required)
Set to OFF 
after setting 
addresses.
ON
Relay connector
Connect after 
setting 
addresses.
Open
Connect after 
setting 
addresses.
Open
Connect after 
setting 
addresses.
Open
 
Line (system) address
1
1
2
2
3
Indoor unit address
1
2
1
2
1
Group address
0
0
1
2
0
A
U1 U2
U3 U4
U3 U4
U3 U4
U3 U4
U3 U4
U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U1 U2
U5 U6
B
A B
A B
A B
A B
Central 
control 
controller
Relay 
connector
Relay 
connector
Relay 
connector
Header unit
Header unit
Header unit
Follower unit
Follower unit
Remote 
controller
Remote 
controller
Remote 
controller
Remote 
controller
Individual
Group
Indoor units 
(automatic setting)
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all 
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
„
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and 
outdoor wiring has not been started (manual setting using the remote controller)
▼ Wiring example of 2 refrigerant lines
In the example above, disconnect the remote controller connections between the indoor units and connect 
a wired remote controller to the target unit directly before address setting.
Pair the indoor unit to set and the remote controller 
one-to-one. 
Turn on the power.
1
Push and hold the 
, and 
 buttons at 
the same time for more than 4 seconds.
LCD starts flashing.
Line (system) address
1
1
1
2
2
Indoor unit address
1
2
3
1
2
Group address
1
Header unit
2
Follower unit
2
Follower unit
2
Follower unit
2
Follower unit
Outdoor 
unit
Outdoor 
unit
Remote 
controller
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
Refrigerant line 1
Refrigerant line 2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT   No.
SETTING
DATA
SET
R.C.
No.
11
4, 7, 10
2, 5, 8
3, 6, 9
1
SET DATA
CODE No.
SET
CL
TEST
49-EN
50-EN
+00EH99871699_01EN.book  Page 25  Thursday, August 26, 2010  4:41 PM