SS-GSH10C
www.goodmanmfg.com
3
S
pECifiCationS
GSH10
0903A*
GSH10
0903B*
GSH10
1203A*
Nominal Capacities
Cooling (BTU/h)
87,000
90,000
110,000
Heating (BTU/h)
84,000
84,000
100,000
EER/IEER
11/--
11/11
11/11.5
Decibels
76
76
77
Compressor
RLA
25.6
25.6
30.1
LRA
196
196
225
Condenser Fan Motor
Horsepower
1
1
1
FLA
5.6
5.6
5.6
Refrigerant Lines
Liquid Valve Size (“O.D.)
⅝"
⅝"
⅝"
Suction Valve Size (“O.D.) (7½ tons)
1⅜"
1⅜"
1⅜"
Suction Valve Size (“O.D.) (10 tons)
1⅝"
1⅝"
1⅝"
Valve Type
Sweat
Sweat
Sweat
Electrical Data
Voltage/Phase
208-230/3
208-230/3
208-230/3
Minimum Circuit Ampacity¹
37.6
37.6
43.2
Max. Overcurrent Protection²
60
60
70
Min / Max Volts
197/253
197/253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
Ship Weight (lbs)
254
254
315
¹   Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require 
larger wire sizes
²  May use fuses or HACR type Circuit Breakers of the same size as noted
Notes
•  Always check the S&R plate for electrical data on the unit being installed.
•  Installer will need to supply 1⅛” to 1⅜” or 1⅛” to 1⅝” as appropriate.
•  Unit charge with dry nitrogen/helium;  must safely dispel holding charge from unit. Evacuate and charge with 
R-22 per Installation Manual.
•  Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS 
DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.