OPERATION DATA
Capacity Control
 The control system cycles
compressor to give capacity control steps as shown in
Tables 
 The unit controls leaving chilled water tem-
perature. Entering water temperature is used by the micro-
processor in determining the optimum time to add or sub-
tract steps of capacity, but is not a control set point.
The chilled water temperature set point can be automat-
ically reset by the return temperature reset or space and out-
door air temperature reset features. It can also be reset from
an external 4-20 
 signal with a loop isolator, or from a
network signal.
The operating sequences shown are some of many pos-
sible loading sequences for the control of the leaving water
temperature. If a circuit has more unloaders than another,
that circuit will always be the lead circuit.
Table 
4A
 Capacity 
Control Steps, 040-070
Compressors
LOADING SEQUENCE 
%
Displacement
2 5
5 0
Bl*
 
,
4
Al 
5
Al ,Bl
1 0 0
1
040 (50 
5 3
4
,
1 0 0
045 (50 Hz)
1
 
A l *
Al
Al 
4
Al 
A l &   *
Al 
Al 
UNIT
3 0 G N
 
,
040 (60 Hz)
045 (60 Hz)
040 (50 Hz)
 
CONTROL
STEPS
1
LOADING SEQUENCE A
%
Displacement
Compressors
A l *
Al 
2 5
A l *
1 0 0
Al 
A l ”
Al 
2 4
 
045 (50 Hz)
3 8
050 (60 Hz)
 
Al 
5
1 0 0
Al 
045 (50 Hz)
5
1 0 0
Al 
1
1 8
045  (50 Hz)
5 6
Al 
6
Al 
7
1 0 0
Al ,Bl
1
045 (50 Hz)
4
6 4
7
 *
Al 
Al 
*Unloaded compressor.
 unloader, standard.
**Compressor unloader, accessory.
 unloaders, both unloaded.
5