WIRING  –  MAIN POWER
Refer to the unit rating plate for wire sizing information 
and maximum fuse or “HACR” type circuit breaker 
size.  Each outdoor unit is marked with a “Minimum 
Circuit Ampacity”.  This means that the field wiring 
used must be sized to carry that amount of current. 
Depending on the installed KW of electric heat, there 
may be two field power circuits required.  If this is the 
case, the unit serial plate will so indicate.  All models 
are suitable only for connection with copper wire. Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions must be adhered 
to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75° C 
copper) for all models including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.
The unit rating plate lists a “Maximum Time Delay 
Relay Fuse” or “HACR” type circuit breaker that is to 
be used with the equipment.  The correct size must be 
used for proper circuit protection and also to assure that 
there will be no nuisance tripping due to the momentary 
high starting current of the compressor motor.
The disconnect access door on this unit may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left-hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.
See “Start Up” section for important information on 
three phase scroll compressor start ups.
See Tables 3 & 4 for Electrical Specifications.
WIRING  –  LOW VOLTAGE WIRING 
All 230/208V, 1 phase and 3 phase equipment have 
dual primary voltage transformers.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 
208V taps are:
 
TAP RANGE
 
240 
253 – 216
 
208 
220 – 187
NOTE:  The voltage should be measured at the field
power connection point in the unit and while 
the unit is operating at full load (maximum 
amperage operating condition).
For wiring size and connections, refer to Wiring 
Manual 2100-507.