TROUBLESHOOTING
FIGURE  8
FAN BLADE SETTING
TABLE  1
FAN BLADE DIMENSION
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of 
refrigerant listed on the serial plate.  AHRI capacity and 
efficiency ratings were determined by testing with this 
refrigerant charge quantity.
The following pressure tables show nominal pressures 
for the units.  Since many installation specific situations 
can affect the pressure readings, this information should 
only be used by certified technicians as a guide for 
evaluating proper system performance.  They shall not 
be used to adjust charge.  If charge is in doubt, reclaim, 
evacuate and recharge the unit to the serial plate charge.
REMOVAL OF FAN SHROUD
  1. Disconnect all power to the unit.
  2. Remove the screws holding both grilles, one on 
each side of unit, and remove grilles.
  3. Remove screws holding fan shroud to condenser 
and bottom.  Nine (9) screws.
  4. Unwire condenser fan motor.
  5. Slide complete motor, fan blade, and shroud 
assembly out the left side of the unit.
  6. Service motor/fan as needed.
  7. Reverse steps to reinstall.
"A"
AIRFLOW
MIS-1724
Model
Dimension
A
W17A2 / W17L2
W18A2 / W18L2
W24A2 / W24L2
1.00"
W30A2 / W30L2
W36A2 / W36L2
1.25"
W42A2 / W42L2
W48A2 / W48L2
W60A2 / W60L2
W70A2 / W70L2
1.75"
FAN BLADE SETTING DIMENSIONS
Shown in Figure 8 is the correct fan blade setting for 
proper air delivery across the outdoor coil.  Refer to 
Table 1 for unit specific dimension.
Any service work requiring removal or adjustment 
in the fan and/or motor area will require that the 
dimensions below be checked and blade adjusted in or 
out on the motor shaft accordingly.