TABLE  4
j
  Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
  Based on 75C copper wire.  All wiring must conform to the National Electrical Code and all local codes.
  These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.
  
   Caution: When more than one field power circuit is run through one conduit, the conductors must be derated.  Pay special attention to note 8 of Table 310 regarding Ampacity  
  Adjustment Factors when more than three (3) current carrying conductors are in a raceway.
 *   Top outlet supply option is available only factory installed and only on the selected models.
    
IMPORTANT:  While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National  
    Electrical Code and all local codes.
  Electrical Specifications — W**L Series
MODEL
Rated 
Volts & 
Phase
No. 
Field 
Power 
Circuits
Single Circuit
Dual Circuit
Minimum 
Circuit 
Ampacity
j
Maximum 
External 
Fuse or 
Ckt. Brkr.
Field 
Power 
Wire 
Size
Ground 
Wire
  Minimum 
Circuit
Ampacity
j
  Maximum
External Fuse 
or Ckt. Breaker
Field Power 
Wire Size
Ground
Wire Size
Ckt. A Ckt. B
Ckt. A Ckt. B
Ckt. A Ckt. B
Ckt. A Ckt. B
W17, 18L2-A00,A0Z
A05
A08
A10
230/208-1
1
1
1
1
16
30
46
56
20
30
50
60
12
10
8
6
12
10
10
10
W24L2-A00, A0Z
A05
A08
A10
230/208-1
1
1
1
1
21
30
46
56
30
30
50
60
10
10
8
6
10
10
10
10
W24L2-B00, B0Z
B06
230/208-3
1
1
15
22
20
25
12
10
12
10
W24L2-C00, C0Z
C06
460-3
1
1
9
11
15
15
14
14
14
14
W30L2-A00*, A0Z*
A05*
A08
A10*
A15
230/208-1
1
1
1
1
1 or 2
24
32
47
58
84
35
35
50
60
90
8
8
8
6
4
10
10
10
10
8
58
26
60
30
6
10
10
10
W30L2-B00*, B0Z*
B09*
B15
230/208-3
1
1
1
18
33
51
20
35
60
12
8
6
12
10
10
W30L2-C00*, C0Z*
C09*
C15
460-3
1
1
1
11
17
26
15
20
30
14
12
10
14
12
10
W36L2-A00*, A0Z*
A05*
A10*
A15
230/208-1
1
1
1
1 or 2
29
32
58
84
35
35
60
90
8
8
6
4
10
10
10
8
58
26
60
30
6
10
10
10
W36L2-B00*, B0Z*
B09*
B15
230/208-3
1
1
1
23
33
51
30
35
60
10
8
6
10
10
10
W36L2-C00*, C0Z*
C09*
C15
460-3
1
1
1
11
16
26
15
20
30
14
12
10
14
12
10
W42L2-A00, A0Z
A05
A10
A15
230/208-1
1
1
1
1 or 2
32
32
58
84
50
50
60
90
8
8
6
4
10
10
10
8
58
26
60
30
6
10
10
10
W42L2-B00, B0Z
B09
B15
230/208-3
1
1
1
24
33
51
35
35
60
8
8
6
10
10
10
W42L2-C00, C0Z
C09
C15
460-3
1
1
1
12
17
26
15
20
30
14
12
10
14
12
10
W48L2-A00, A0Z
A05
A10
A15
230/208-1
1
1
1
1 or 2
39
39
58
84
50
50
60
90
8
8
6
4
10
10
10
8
58
26
60
30
6
10
10
10
W48L2-B00, B0Z
B09
B15
230/208-3
1
1
1
27
33
51
40
40
60
8
8
6
10
10
10
W48L2-C00, C0Z
C09
C15
460-3
1
1
1
13
17
26
20
20
30
12
12
10
12
12
10
W60L2-A00, A0Z
A05
A10
A15
230/208-1
1
1
1
1 or 2
42
42
60
86
60
60
60
90
8
8
6
3
10
10
10
8
60
26
60
30
6
10
10
10
W60L2-B00, B0Z
B09
B15
230/208-3
1
1
1
28
35
53
40
40
60
8
8
6
10
10
10
W60L2-C00, C0Z
C09
C15
460-3
1
1
1
15
18
27
20
20
30
12
12
10
12
12
10
W70L2-A0Z
A05
A10
A15
230/208-1
1
1
1
1 or 2
56
56
59
85
60
60
60
90
6
6
6
4
10
10
10
8
59
26
60
30
6
10
10
10
W70L2-B0Z
B09
B15
230/208-3
1
1
1
38
38
53
60
60
60
8
8
6
10
10
10
W70L2-C0Z
C09
C15
460-3
1
1
1
19
19
27
30
30
35
10
10
18
10
10
10