II. Initial Start
Safe lighting and other performance criteria were met when
testing various gas manifold and control assemblies used
on the Victory VSP Series Boilers under the ANSI Z21.13-
latest edition.
Instructions
Follow  the lighting instructions in this manual. These 
instructions are also attached to the boiler.
SAFETY INFORMATION
For Your Safety Read Before Operating
A. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot by
hand.
B. BEFORE OPERATING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
•  DO NOT try to light any appliance.
• DO NOT touch any electric switch: DO NOT use any
phone in your building.
•  Immediately call you gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•  If you cannot reach your gas supplier, call the fire depart-
ment.
C. Use only your hand to turn the gas control knob. Never 
use tools. If the knob will not turn by hand, don’t try to 
repair it, call a qualified service technician. Force or 
attempted repair may result in a fire or explosion.
D. Do Not use this appliance if any part has been under 
water. Immediately call a qualified service technician to 
inspect the appliance and to replace any part of the 
control system and any gas control which has been under 
water.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which
automatically lights the pilot. DO NOT try to light the pilot by
hand.
5. Remove jacket front panel
6. Turn gas control knob clockwise            to “OFF”.
DO NOT force.
7. Wait five (5) minutes (longer for propane) to clear out any 
gas, then smell for gas, including near the floor. If you then 
smell gas, STOP! Follow “B” in the safety information 
above on this page. If you don’t smell gas, go to next 
step.
8.
Turn as control knob counterclockwise            to “ON”.
9.
Replace jacket front panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions 
“To Turn Off Gas to Appliance” and call your service 
technician or gas supplier.
To Turn Off Gas to Appliance
1.
Set thermostat to lowest setting.
2.
Turn off all electric power to the appliance if service 
is to be performed.
3.
Remove jacket front panel.
4.
Turn gas control knob clockwise             till knob stops, 
then continue to “OFF”. Do not force.
5.
Replace jacket front panel.
Removing Jacket Front Panel
1.
Turn black screws 
1
4
turn to open position.
2.
Remove front panel.
To replace the panel, reverse procedure.
Gas Input Rate Adjustment
1.
Consult gas supplier for higher heating value* of gas 
(Btu/cu. ft.)
2.
Set thermostat high enough so that boiler will remain on 
3.
Measure manifold pressure.
Correct manifold pressure for gas used is printed on boiler 
rating plate. NOTE: Gas pressure may be adjusted by 
turning pressure regulator screw on combination gas valve 
(turn clockwise to increase pressure, counterclockwise to 
decrease pressure).
*  ”Higher Heating” value of gas is commonly known as “heating value”.
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property
damage, personal injury or loss of life.
0FF
0FF
ON
ON
HON EYWELL
HON EYWELL
 GAS
 GAS
INLET
INLET
GAS 
CON TRO L 
KNO B
GAS 
CON TRO L 
KNO B
SHO W N 
IN 
"O FF"
SHO W N 
IN 
"O FF"
PO SITI
ON
PO SITI
ON
OUTLET
OUTLET
VSP40-19
VSP40-19
FIGURE 
19
FIGURE 
19
Figure 19.
Gas Valve VR8204  or VR8304