SAFETY CHECK
A. Check for gas leaks:
Using soap solution, check for gas leaks from meter to gas 
valve including all pipes and fittings and gas valve 
connections. Use liquid soap solution for all gas testing. DO
NOT use open flame.
B. Thermostat Test:
Set thermostat setting to low enough to end call for heat.
Gas valve should close and burner should stop firing.
Blower and circulator pump should go into a post purge, 
then shut off.
C. Control Safety Shutdown test:
With the burner firing, disconnect the spark cable from the 
spark ignitor. Gas valve should close and burner should 
stop firing. The boiler will try for ignition three times after 
this, then should lock out with an “A 01” error shown on the
display. Reconnect the spark cable to the spark ignitor, and 
press the “Reset” button to return to normal operation.
VI. DIAGNOSTIC ERROR CODES
WARNING: Only a trained, experienced service technician
should perform troubleshooting. Turn off all electric power to the
boiler before service.
A. LOCKOUT ERRORS: Indicated by an “A” in the  mode display. The reset button must be pressed to clear the error 
and retry operation. The temperature display shows the error code.
ERROR CODE
INDICATION
REMEDY
01
Ignition Failure - 3 unsuccessful 
ignition attempts in a row.
Check for steady sparking at electrodes. If spark not
steady - check spark gap to be .125”, clean or replace
spark ignitor, check power supply voltage and grounding.
If spark is steady - check for proper gas supply pressure.
Check combustion, if able to ignite, or replace gas valve.
02
Flame Failure - 3 losses of flame
signal during one demand.
Check for proper combustion, at both max. and min.
input firing rates. If combustion is within the range 
specified on page 37, clean or replace spark ignitor,
check power supply voltage and grounding.
03
Water High Limit Open
Check to see if the water outlet temperature reaches
203˚F. If it does, replace the water outlet 12k ohm 
sensor. If it does not, replace the water high limit switch.
04, 05, 09, 10,
12, 13, 14, 15,
16, 18, 32
Control Failure
Replace control board. Make sure the proper boiler
model selection and confirmation code is entered.
See Table 5 on page 33.
19, 20
Flame Detected at Wrong Time
If a flame is still observed after a call for heat is stopped,
replace the gas valve. If the burner seems to be shutting
down properly, replace the spark ignitor.
33
Fan Failure -  RPM error
Check wire harness connections going to the blower.
Replace blower.