S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
28
Stack Limit Configuration Parameters
Table 20 displays stack limit configuration parameters.
Fig. 48. Stack Limit configuration.
Delta T Limit Configuration 
Parameters 
(R7910A Hydronic Control Only)
Table 21 displays other limit parameters. Use the left and right 
arrows to switch between Inlet to Outlet Flow and Exchanger to 
Outlet Flow. The parameters are the same for all pumps.
Fig. 49. Delta T Limit configuration.
Table 20. Stack Limit Configuration Parameters.
Parameter Comment
Stack limit
Enabled dual sensor safety
Enabled single sensor non safety
Disabled
Stack limit delay
___hour ___min ___sec
Stack limit response
Lockout
Recycle & delay
Stack limit setpoint
32 °F to 266 °F (0 °C to 130 °C)
Table 21. Delta T Limit 
Configuration Parameters.
Parameter Comment
Delta T enable
Enabled
Disabled
Delta T degrees
0 °F to 234 °F (-17 °C to 112 °C)
Delta T delay
___hour ___min ___sec
Delta T response
Recycle & delay
Recycle & Delay with retry limit
Lockout
Delta T retry limit
0–100
Delta T rate limit 
enable
Enabled
Disabled
Delta T inverse limit 
time
___hour ___min ___sec
Delta T inverse limit 
response
Recycle & delay
Recycle & delay with retry limit
Lockout