Справочник Пользователя для Honeywell S7999B

Скачать
Страница из 68
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
65-0303—05
4
required to correct the interference at his own expense.
This Class A digital apparatus complies with Canadian ICES-003.
Cet Appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
 SAFETY FEATURES
The OI Displays contain software that incorporates many 
features that are designed to guide you safely through the 
commissioning process. Safety, however, is your responsibility.
Read all documentation carefully and respond appropriately to 
all error messages.
WARNING
Explosion Hazard.
Improper configuration can cause fuel buildup and 
explosion.
Improper user operation may result in PROPERTY 
LOSS, PHYSICAL INJURY or DEATH.
Using the OI Displays to change parameters, must be 
attempted by only experienced and/or licensed 
burner/boiler operators and mechanics.
INSTALLATION INSTRUCTIONS 
(S7999B OI DISPLAY)
NOTE: For S7999C OI Display installation instructions, see 
Mounting the S7999B OI Display and 
Power Supply
The OI Display can be mounted on the door panel of an 
electrical enclosure.
1. Select the location on the door panel to mount the dis-
play; note that the device will extend into the enclosure 
at least one inch past the mounting surface.
2. Provide an opening in the panel door 8-1/8 in. wide by 5-
7/8 in. high.
3. Place the OI Display in the opening and use it as a tem-
plate to mark the location of the four mounting screw 
holes. Remove the device.
4. Using pilot holes as guides, drill 1/4 in. holes through the 
door panel.
5. Place the display in the opening, aligning the mounting 
holes in the device with the drilled holes in the panel.
6. Secure the display to the panel with four #6-32 screws 
and nuts provided.
Fig. 2. S7999B OI Display connector terminals.
7. Select a location inside the enclosure for mounting the 
power supply.
8. Using the power supply as a template, mark the loca-
tions of the two mounting holes in the enclosure.
9. Remove the power supply.
10. Drill 1/4 in. holes through the panel at the marked loca-
tions and secure the power supply with the two #6-32 
screws and nuts provided.
11. Remove the 9-pin connector plug from the back of the OI 
Display.
12. Wire the connector to the power supply and the RS-485 
cables using the wiring diagram in Fig. 3.
13. Ensure the 9-pin connector plug is aligned with the 
header pins when inserting the 9-pin connector plug 
back onto the Display. Secure firmly.
WIRING (S7999B OI DISPLAY)
The S7999B OI Display must be appropriately wired for both 
power and communications. An external 12V power supply 
(provided) with an appropriate power rating is connected to 
pins 1, 2 and 3 to power the device.
Communication is done over a RS-485 bus:
• COM1 connected directly to the SOLA Device J3 connector 
to either Modbus (MB1 or MB2).
• COM2: A bus to the Building Automation System.
See Fig. 2 for S7999B Display connector terminals. Wiring 
connections are listed in Table 1. See Fig. 3 for wiring.
Table 1. 9-pin Connector Terminals
Pin #
Function
1
12V input
2
12V input
3
Common (Power, COM 1)
4
COM 1 (b) to MB1 or MB2 terminal
5
COM 1 (a) to MB1 or MB2 terminal
6
Not used
7
Not used
8
COM  2  (a)
1     2     3     4    5     6     7     8     9
M28859A
COMMON (c)
COM1 (b)
COM1 (a)
N/C
N/C
COM2 (a)
COM2 (b)
      +12V