Справочник Пользователя для Majestic Appliances NVBR36

Скачать
Страница из 24
17
Majestic Fireplaces
®
 NVB Series B-Vent
7412950
FP649
• Turn gas supply off
• Turn ON/OFF Switch
  to call for heat. 
NO
NO
NO
NO
NO
NO
NO
Spark across
Ignitor Sensor gap
Power to module
(24V nominal)
YES
YES
YES
YES
YES
YES
YES
• Turn gas on
Pilot burner lights?
Spark stops when pilot 
is lit?
Main Burner lights?
• Replace Module
START
• Line Voltage (120VAC)
• Low Voltage Transformer
  (19.5 minimum VAC)
• ON/OFF Switch
• Wiring connections
• Thermodisk
•  Check continuity of ignition cable and ground wire.
•  Clean flame rod.
•  Check electrical connections beween flame rod and module.
•  Check for cracked ceramic flame rod insulator.
•  Check that pilot flame covers flame rod and is steady blue.
•  Adjust pilot flame.
•  If problem persists, replace module.
Unplug Ignition Lead
and check spark
at module
(24VAC nominal) 
Spark OK?
•  Check ignition cable, ground wiring, Ceramic Insulator and gap. Correct as necessary
•  Check boot of ignition cable for signs of melting or buckling. Take protective
   actions to shield cable and boot from excessive temperatures.
•  Check for 24VAC across MV-MV/PV terminals. If no voltage, replace module.
•  Check electrical connections between module and gas control. If okay, replace gas 
   control or gas control operator.
•  Check for continuity of igniton cable and ground wire. NOTE: If ground is poor or 
   erratic, shutdowns may occur occasionally even though operation is normal
   at time of checkout.
•  Check that the pilot flame covers flame rod and is steady and blue.
•  If checks are okay, replace module.
Troubleshooting
Ends
•  Check that all manual gas valves are open, supply tubing and pressures are good,
   and pilot burner orifice is not blocked.
•  Check electrical connections between module and pilot operator on gas control.
•  Check for 24VAC across PV-MV/PV terminals on module. If voltage is okay, replace
   gas control. If not, replace module.
NOTE: If S8600B goes into lockout, reset system.
NOTE: If S8600B goes into lockout, reset system.
CHECK :
System runs until
ON/OFF switch is in
"OFF" position
Troubleshooting
Remove glass panel before servicing.
NOVA SIT 822 with Honeywell S8600 B Electronic Ignition