Regency Freestanding Woodstove
14
MOBILE HOME INSTALLATION
Once you have properly marked the position 
of your unit and the fl oor protection as outlined 
in the Residential Installation items #1 through 
#8, a supply of fresh air has to be supplied to 
your unit. Cut a minimum 4 inch diameter hole 
through your fl oor protector and the fl oor directly 
under your pedestal base to the outside.  Use 
4" duct pipe with a mesh grill to pipe fresh air 
into the pedestal area. Block off the hole in the 
back of the pedestal with the square plate and 
the two 1/2" (13mm) screws provided.
Place your unit in position and secure it to the 
fl oor using two lag bolts 3/8" x 3-1/2" (10mm x 
89mm) through the two holes inside the pedestal 
base.  It is important to maintain the structural 
integrity of the Mobile Home fl oor, walls and roof 
when installing your unit.
For Mobile Home units installed in the U.S. the 
unit must be grounded using a #8 ground wire 
with approved termination and star washer.
In addition to standard installation instructions 
the following requirements are mandatory for 
installation in a mobile home.
1) The stove must be permanently bolted to 
the fl oor of the Mobile Home using the fl oor 
screws provided.
2) The stove must have a permanent outside 
air source for combustion.
3) The stove must be electrically grounded to 
the steel chassis of the Mobile Home. 
4) A listed double-wall connector chimney 
system, roof thimble, spark arrestor and roof 
fl ashing kit suitable for use in Mobile Homes 
must be used.
5) If the chimney exits the Mobile Home at a 
location other than through the roof, and exits at 
a point 7ft. (2130mm) or less above the ground 
level on which the Mobile Home is positioned 
a guard or method of enclosing the chimney 
shall be fi tted at the point of exit for a height up 
to 7ft. (2130mm).
6) The chimney shall be attached directly to 
the room heater and shall extend at least 3 ft. 
(914mm) above the part of the roof through 
which it passes. The top of the chimney should 
project at least 2ft. (610mm) above the highest 
elevation of any part of the Mobile Home within 
10 ft. (3048mm) of the chimney.
7) The chimney system shall comply with Local 
Requirements.
8)  Any openings in a chimney guard where 
required must not permit the entrance of 3/4" 
(19mm) diameter rod.
9) CAUTION: THE STRUCTURAL INTEGRITY 
OF THE MOBILE HOME ROOF, FLOOR, 
WALLS AND CEILING MUST BE MAIN-
TAINED.
10) Check any other local building code as other 
local codes may apply.
11) WARNING: DO NOT INSTALL IN A SLEEP-
ING ROOM OF A MOBILE HOME.
12) Use silicone to create an effective vapour 
barrier at the location where the chimney or 
other component penetrates to the exterior of 
the structure.
INSTALLATION
CAUTION:  At no time use unlabelled 
parts, or substitute parts made for another 
chimney system.
Install as per chimney manufacturer's 
installation instructions.
WARNING: Operate only with door fully 
closed - open feed door to feed fi re only.