Quadra-Fire  •  Sapphire  •  7055-116  Rev. D  •  6/11
INDIVIDUAL INSTALLATIONS MAY VARY.  
Percentage closed based on full range of the fl ue restric-
tor travel.
D. How to Use the Vent Graph
1.  Measure the distance from the top of appliance to the 
center of the 90° elbow. On the graph below, draw a 
horizontal line from that measurement on the vertical 
axis across until it intersects with the slanted line.
2.  From the point of this intersection, draw a vertical line to 
the bottom of the graph.
3.  The point at which this line meets the bottom line of the 
graph is the maximum length of the horizontal run. 
EXAMPLE 1: If the vertical dimension from the center line 
of the fl ue vent to the center of the 90° elbow is 7 ft. (2 m), 
the horizontal run to the outer wall fl ange must not exceed 
13 ft. 2 in. (5m).
EXAMPLE 2: If the vertical dimension from the center line 
of the fl ue vent is 21 ft. (6m), the horizontal run to the outer 
wall fl ange must not exceed 10 ft. (3m).
4.  Each 90° elbow is equivalent to 3 ft. (914mm) of vent 
pipe and each 45° elbow is equivalent to 1 ft. (305mm) 
of vent pipe, and must be subtracted from vent pipe 
run. A single vertical to horizontal 90° elbow is already 
calculated into the allowable 15 ft. (5m) run. Each 
additional 90° elbow reduces the maximum horizontal 
distance by 3 ft. (914mm).
Figure 5.2
TOTAL HORIZONTAL RUN TO THE OUTER 
WALL FLANGE (EXCLUDING ELBOWS)
E. Venting Guidelines for Horizontal Runs
Max Horizontal Run, 
Rear Vent
3 ft (914mm)
Max Horizontal Run
15 ft (5m) when vertical rise is 
10 ft (3m
Max Horizontal Run 
with 45
o
 Elbow
14 in. (356mm)
Min Horizontal Run
11 in. (279mm)
Max Wall Thickness
20 in. (508mm)
Min Wall Thickness
4 in. (102mm)
Exterior Vent Diameter
6-5/8 in. (168mm)
Inner Vent Diameter
4 inches (101mm)
Rear Vent with Vertical 
Rise
Min of 2 ft vertical (610mm) 
must be used prior to any hori-
zontal run
Horizontal Run requires a 1/4 in. (6mm) rise for every 1 ft 
toward the termination. 
Horizontal Run requires a non-combustible support every 
3 ft (914mm), i.e., plumbing tape
Standard Horizontal Run 
Horizontal Run with Snorkel Kit. 
A rear vent configuration with 3 ft. (914mm) maximum 
horizontal run with no vertical pipe and with 1/4 in. 
(6mm) rise per foot.
•  A snorkel kit must be used. 
Figure 5.3 below and 
Figure 5.4 on page 12.
•  A derating orifice must be installed. The appropriate 
orifice is supplied with the rear vent kit.
WARNING! Fire Risk! 
•  Never allow the vent to run downward.
•  This could cause high temperatures and may present 
the possibility of a house or structure fi re.
Example:  The use of 3 elbows would reduce the 
allowable horizontal run to 9 ft. (3 - 1 = 2 elbows x 3 ft. = 
6 ft.; 15 ft. max. - 6 ft.= 9 ft. max.)
Example 2
     11"   2'        4'         6'        8'       10'      12'      14'  15'
30'
28'
26'
24'
22'
20'
18'
16'
14'
12'
10'
 8'
 6'
 4'
 2'
 0'
(MAX)
(MIN)
40'
38'
36'
34'
32'
Example 1
Vertical Distance 
from Appliance Top 
to 90
o
 Elbow
40 ft. (12m) 
Maximum Run if 
using Stainless 
Steel Inner Pipe 
Material
30 ft. (9m) Maxi-
mum Run if using 
Aluminum Inner 
Pipe Material
Flue Restrictor more 
CLOSED in this area
Flue Restrictor 
50% CLOSED in 
this area
Flue Restrictor 
OPEN in this area
NOTE: IF YOUR INSTALLATION FALLS WITHIN 
A SHADED AREA ON THE GRAPH, THE FLUE 
RESTRICTOR MUST BE USED. 
C
L
Snorkel Kit
Figure 5.3