Справочник Пользователя для Procom SL250TYLA-D

Скачать
Страница из 21
   5
       
WARNING:   Rework   worksheet,  adding   the  space  of   the  adjoining  unconfined  space.  The
combined  spaces  must   have  enough  fresh air  to supply  all  appliances  in  both  spaces.
If  the actual  Btu/Hr  used  is  less  than  the  maximum  Btu/Hr  the  space  can  support, the  space  is  an
unconfined  space. You  will  need  no  additional  fresh  air  ventilation.
3. Add  the  Btu/Hr of all fuel burning appliances in the space.
     Vent-free heater                                                      Btu/Hr
     Gas water heater*                                                   Btu/Hr
     Gas furnace                                                            Btu/Hr
     Vented gas heater                                                   Btu/Hr
     Gas heater logs                                                       Btu/Hr
     Other gas appliances* +                                          Btu/Hr
     Total                                =                                       Btu/Hr
    *Do  not  include  direct-vent  gas  appliances. Direct-vent  draws  combustion  air  from  the  outdoors  and
       vents to the outdoors.
4. Compare  the  maximum  Btu/Hr  the  space  can  support  with  the  actual amount of Btu/Hr used.
                         Btu/Hr (maximum the space can support)
                          Btu/Hr (actual amount of Btu/Hr used)
         Example :  51,200 Btu/Hr(maximum the space can support)
                           56,000 Btu/Hr(actual amount of Btu/Hr used)
The  space  in  the  above  example  is  a  confined  space  because  the  actual  Btu/Hr  used  is  more  than  the
maximum  Btu/Hr  the  space  can  support.
You  must  provide  additional  fresh  air.  Your  options  are  as  follows:
A.  Rework  worksheet, adding  the  space  of  an  adjoining  room. If  the  extra  space  provides  an  unconfined
space, remove  door  to  adjoining  room  or  add  ventilation  grills   between  rooms. See  Ventilation  Air  From
Inside  Building
 (below).
B.  Vent  room  directly  to  the  outdoors. See  Ventilation  Air  From  Outdoors (below) .
C.  Install  a  lower  Btu/Hr  heater, if  lower  Btu/Hr  size  makes  room  unconfined.
Figure  2 -Ventilation  Air  from  Inside  Building
 Example:
Gas  water  heater          30,000        Btu/Hr
Vent-free  heater    +      26,000        Btu/Hr
  Total                          =   56,000       Btu/Hr
        
 WARNING:  If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as
an  unconfined space or  if  the building  is  of  unusually  tight  construction, provide  adequate
combustion  and  ventilation air by  one of   the  methods  described  in  the  National Fuel  Gas  Code,
ANS  Z223.1, Section  5.3  or  applicable  local  codes.
This  fresh air  would come  from an adjoining  un-
confined space.  When  ventilating  to  an  adjoining
unconfined space, you  must  provide  two  perma-
nent  openings: one within 12" of  the  ceiling  and
one  within 12" of  the  floor on  the  wall  connecting
the  two  spaces (see  options 1 and  2, Figure 2).
You  can  also  remove  door  into adjoining  room
(see  option 3, Figure 2). Follow  the  National  Fuel
Gas  Code. NFPA  24/ANS  Z223.1.  Section 5.3,  Air
for  Combustion  and  Ventilation  for required size of
ventilation grills or ducts.
Ventilation  Air  From  lnside  Building
Ventilation  Air  From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12" of
the floor. Connect these items directly to the out-
doors or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the National
Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3.
Air for Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT:Do not provide openings for  inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the
attic will activate the power vent.
Figure  3 -Ventilation  Air  from  Outdoors