Mt. Vernon Pellet Insert (AE)
6
Mobile Home
1. 
An outside air inlet must be provided for the combustion 
air and must remain clear of leaves, debris, ice and/or 
snow.  It must be unrestricted while the appliance is 
in  use  to  prevent  room  air  starvation  which  causes 
smoke spillage.  Smoke spillage can also set off smoke 
alarms.  
2. 
The combustion air duct system must be made of metal.  
It must permit zero clearance to combustible construc-
tion and prevent material from dropping into the inlet or 
into the area beneath the dwelling and contain a rodent 
screen.
3. 
The  appliance  must  be  secured  to  the  mobile  home 
structure  by  bolting  it  to  the  fl oor  (using  lag  bolts).  
Use the same holes that secured the appliance to the 
shipping pallet.
4. 
The appliance must be grounded with #8 solid copper 
grounding wire or equivalent, terminated at each end 
with an NEC approved grounding device.
5. 
Refer  to  Clearances  to  Combustibles  and  fl oor  pro-
tection  requirements  on  pages  8  &  9    for  listings  to 
combustibles and appropriate chimney systems.
6. 
Use  silicone  to  create  an  effective  vapor  barrier  at 
the  location  where  the  chimney  or  other  component 
penetrates to the the exterior of the structure.
7. 
Follow the chimney manufacturer’s instructions when 
installing the vent system for use in a mobile home.
8. 
Installation shall be in accordance with the Manufactur-
ers Home & Safety Standard (HUD) CFR 3280, Part 
24.
NEVER INSTALL IN A SLEEPING ROOM.
WARNING
You must use a Quadra-Fire Outside Air Kit 
for installation in a mobile home.
Spark Arrestor Cap
Roof Flashing 
Storm Collar 
Joist Shield/Firestop 
Approved Class L 
or PL Pellet Vent
Figure 19.1
CAUTION
Never draw outside combustion air from:
•  Wall, fl oor or ceiling cavity
•  Enclosed space such as an attic or garage
CAUTION
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME 
FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED
Do NOT cut through:
•  Floor joist, wall, studs or ceiling trusses.
•  Any supporting material that would affect the structural 
integrity.