Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be 
displayed:
The Program Check feature allows the programmer to view the zones which have been 
programmed to the Notification Appliance Circuits on the control panel but have not been 
programmed to Initiating Devices as well as other circuits with no input or output 
correlations.  Pressing 1 while viewing Program Check screen will cause a screen similar 
to the following to be displayed. 
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 
and 67 but no input devices have been programmed to any of these zones.  Use the up and 
down arrow keys to view all the NAC zones without input assignments for both NAC 1 
and NAC2.
Pressing 2 while viewing the Program Check screen will display a screen similar to the 
following: 
The Zone No Input screen allows the programmer to view the zones which have not been 
programmed to at least one input device (not including general alarm Zone 00). The 
example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been 
programmed to an addressable module (control module in this example) with an address 
of 001 on loop 1 but have not been programmed to any input devices.  Use the up and 
down arrow keys to view all the zones without input assignments.
    PROGRAMMING
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
Maintenance Screen #1
@@@@PROGRAMCHECK
1=NACS@NO@INPUT
2=ZONES@NO@INPUT
3=ZONE@NO@OUTPUT
Program Check Screen   
@@@NACS@NO@INPUT
NAC@1
@@@@25@31@44@55@67
@@@ZONES@NO@INPUT
05@07@09@10@11@1M001