4.19  Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program an initiating device to delay panel 
activation (including alarm relay and communicator) for a period of 15 seconds.  Zone 97, 
however, will activate immediately and may be used to connect a signaling device to 
indicate PAS activation.  
'RQRWDVVLJQ=RQHWRD1RWLILFDWLRQ$SSOLDQFH&LUFXLWZKHQ
XVLQJWKLV]RQHWRLQGLFDWHD3$6FRQGLWLRQ
When a detector or monitor module triggers an alarm, the onboard piezo sounds 
immediately, but the NACs are prevented from activating for 15 seconds.  This inhibit 
time is factory set and cannot be changed.  Pressing the Alarm Silence or Acknowledge/
Step key during the 15 second inhibit time will silence the piezo sounder and start a timer 
which prevents activation of NACs for an additional time duration which can be user 
programmed for up to three minutes.  After the programmed delay, the NACs will activate 
if the source of the alarm is not cleared.  Note that if a second alarm occurs during either 
time delay, the alarm will be processed immediately, causing activation of the appropriate 
output zones.  The events which occur upon PAS activation are as follows:
✓ onboard piezo sounds immediately
✓ control panel LCD display will indicate a presignal event and the active point
✓ control points programmed to Zone 97 will activate
✓ annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and 
zone LED
✓ outputs (NACs and control modules) of associated zones will be inhibited from 
activating for a factory set duration of 15 seconds
✓ pressing the Alarm Silence or Acknowledge/Step key will start a timer which 
inhibits output activation for additional time delay of up to three minutes which 
is user programmable
✓ second alarm occurring anytime during either time delay will cause immediate 
activation of all associated outputs
PAS does not affect monitor modules programmed as waterflow, supervisory, process 
monitoring or remote switches.  PAS operation requires the approval of the local Authority 
Having Jurisdiction
.
Note that the PAS BYPASS monitor type code, when activated, will inhibit the PAS 
capability until the PAS BYPASS monitor is deactivated.  While PAS is inhibited, signaling 
devices will immediately place the control panel into alarm.  This feature may be 
employed by wiring a normally open device, such as a switch, to a monitor module which 
has been  programmed for PAS BYPASS.