2SHUDWLQJ,QVWUXFWLRQV
5HDG6WDWXV

8QLPRGH31&
4.22.3  Power
Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be 
displayed:
A real-time display of the control panel voltages can be used to determine if a problem 
exists in the system.
The following table lists the circuit being measured, possible conditions and their 
respective voltage ranges:
4.22.4  Trouble Reminder
Pressing 1 while viewing Read Status Screen #2 will display the following screen:
The screen indicates whether the Trouble Reminder feature is On or Off.  
Circuit
Condition
Voltage Range
Battery
Normal Battery (nominal)
27.05 - 28.15 VDC
Low Battery
20.0 - 20.8 VDC
No Battery
0 - 18.36 VDC
24V Resettable
Normal
21.25 - 27.50 VDC
24V Nonresettable
Normal
21.25 - 27.50 VDC
Charger
Normal
27.05 - 28.15 VDC
NAC 1 or NAC 2
Normal
1.37 - 1.43 VDC
Open Circuit
2.30 - 2.40 VDC
Short Circuit
0 - 1.0 VDC
       POWER
BATTERY       27.21V
24 V RST      25.31
24 V NRST     25.31
Zones Screen #1  
       POWER
CHARGER       28.36V
NAC 1          2.39V
NAC 2          2.39V
Zones Screen #2  
    READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NAC
Read Status Screen #2
  TROUBLE REMINDER
TROUBLE REM       ON